2.3 Safe operation procedures
► Before connecting and disconnecting test objects, verify that all outputs have been turned off and
the installation is dead. Never connect or disconnect a test object while the outputs are active.
► When disconnecting power supply cables or test leads, always start from the device feeding the
power or signal.
► Do not operate
VBO3
when explosive gas or vapors are present.
► Only work in well lit areas. If there is not enough daylight, use a strong light to make sure that you
see everything and so ensure your safety.
► Keep your work area clean to avoid accidents.
► If
VBO3
seems to be functioning improperly or has visible damages, please contact the OMICRON
Technical Support (→ page
2.4 Operator qualifications
► Working on a power distribution network can be extremely dangerous. Familiarize yourself
thoroughly with all the information in this manual. In addition, you need to be familiar with all
manuals of the devices used in the test procedure.
► Testing with
VBO3
shall only be carried out by authorized and qualified personnel. Before starting
to work, clearly establish the responsibilities of all personnel involved.
► Personnel receiving training, instruction, direction, or education on
VBO3
shall remain under the
constant supervision of an experienced operator while working with the equipment.
► Personnel operating
VBO3
must be familiar with recognized operating practices and procedures
for working on high and low voltage systems. They must be familiar with the five safety rules:
•
Disconnect completely.
•
Secure against re-connection.
•
Verify that the installation is dead.
•
Carry out grounding and short-circuiting.
•
Provide protection against adjacent live parts.
► In addition, the personnel operating
VBO3
must be familiar with all necessary personal safety
equipment.
► Testing with
VBO3
must comply with all on-site procedures and methods for personal safety and
the safety instructions relevant for each test. They must be discussed with all personnel involved.