background image

RhinoBond Owner’s Manual

  Page 5

 

 SAFE START UP & SHUT DOWN 

 

Unstable generator power during start-up increases the risk of damage to RhinoBond Tools.

 

  

WARNING                

 

Failure to follow these instructions may cause damage 

                                                         to your RhinoBond tool.  

 

 

NEVER

 start generator with tool plugged in. 

ALWAYS

 start generator first, then plug in tool. 

WHEN NOT IN USE,

 unplug the tool.

 

Start portable generator and allow to warm up for 2 minutes. 

Auto-Throttle, Auto-Idle and/or Eco-Idle switches must be in OFF position.

 

Simply unplug the RhinoBond tool to shut down. When resuming work, confirm that generator is running at full speed and delivering stable power before plugging in 

the RhinoBond tool. 

INSULATION COMPATIBILITY 

RhinoBond is compatible with polyisocyanurate, mineral wool and hard cover boards as well as any insulation that will not melt by the induction welding process. 

When using RhinoBond over XPS, EPS, use a minimum 1/4-in. (6 mm) thick cover board or 4-in. (102 mm) diameter cardboard discs under each plate to protect the 

insulation from melting. On foil faced insulation, the recommended minimum cover board is 1½-in. (38 mm). 

Metal Deck

 

A minimum of 1½-inches (38 mm) of insulation over a metal deck is required for proper tool operation. 

PROPER FASTENER INSTALLATION

 

Always follow the roof system manufacturer’s fastening patterns for field, perimeter, and corner areas needed to achieve desired wind ratings (i.e.: FM 1-90, FM 

1-120, etc.).
Fasteners installed in a straight row in a least one direction with even spacing makes locating fasteners under the membrane easier and speeds installation.

 

Snap chalk lines to lay-out fastener grid pattern for field, perimeters, and corners.
Fasteners must not be overdriven.  Plates should be tight enough that you cannot turn them with your hand.  Overdriven fasteners are harder to find and may result 

in a poor or partial bond.

UV EXPOSURE

RhinoBond Plates must be protected from prolonged UV (ultra violet) sun exposure. Installed RhinoBond plates must be covered with membrane by the end of each 

workday. Keep RhinoBond buckets covered when not retrieving plates.  

Too tight;  

insulation 

buckles

Proper  

installation

Too loose; 

plate spins

Содержание RBT007

Страница 1: ...v 06252020 153 BOWLES ROAD AGAWAM MA 01001 USA 800 633 3800 413 789 0252 RHINOBOND COM Non penetrating fastening system for commercial roofing IMPORTANT Save this manual and read it in full before use...

Страница 2: ...le easy to use system that secures membrane to roofing substrates using micropro cessor controlled induction welding Roofing installed this way has several benefits Fewer Fasteners RhinoBond requires...

Страница 3: ...conditions Keep the tool dry at all times ALWAYS ENSURE that the tool is properly grounded CFCI Circuits are best and that power is from a safe and reliable source ALWAYS WEAR proper personal protecti...

Страница 4: ...z 220V 50Hz EXTENSION CORD 12 gauge min 100 ft max 110V 2 5mm X 30m 16A 230V 3x15 30m 10A 30m PORTABLE GENERATOR POWER SOURCE 5 000W min with 2 20A GFCI Circuits 2 5 KVA min with 16Amp 110V protected...

Страница 5: ...s under each plate to protect the insulation from melting On foil faced insulation the recommended minimum cover board is 1 in 38 mm Metal Deck A minimum of 1 inches 38 mm of insulation over a metal d...

Страница 6: ...progress If necessary you can calibrate the touch screen at this time To do so touch this screen once to begin the calibration process see below Once startup is complete the screen will display the L...

Страница 7: ...es can be reviewed Power Display The Power Display shows the line voltage the tool is receiving from the power source The tool requires a minimum of 100 volts to operate effectively Menu Pressing this...

Страница 8: ...ce of membrane from the project weld each plate and apply a magnetic heat sink to each Allow plates to cool to the touch approx 5 minutes before removing the magnetic heat sinks Turn the membrane over...

Страница 9: ...gy Level setting push the plus or minus buttons Push the Home button once the energy setting is set The screen will automatically return to the Device Ready screen The Device Ready screen will display...

Страница 10: ...gnetic cooling clamp on the plate and mark the energy setting on the membrane for reference Adjust the Energy Level to the next higher setting and repeat the test weld process until all five plates ar...

Страница 11: ...arrow to return to the previous screen Press the Sound button to change the Activation Complete tone The sound can be enabled by press ing the On button and disabled by pressing the Off button You ha...

Страница 12: ...t factory reset Press the Home button to return to the Device Ready screen Press the back arrow to return to the previous screen From the main Menu press the Help button to access OMG Roofing Products...

Страница 13: ...main Menu press the Help button to review the Troubleshooting tips and error message descriptions Press any of the error message buttons to get more information and recommendations Press the back arro...

Страница 14: ...Voltage Directive LVD 2006 95 EC The following harmonized standards were applied LVD EN60335 1 2012 A11 2014 EN60335 2 45 2002 A2 2012 RhinoBond Induction Welding Tools wielding the CE Mark comply wi...

Страница 15: ...RhinoBond Owner s Manual Page 15 NOTES...

Страница 16: ...OMG Roofing Products 153 Bowles Road Agawam MA 01001 USA 800 633 3800 413 789 0252 www rhinobond com...

Отзывы: