OMEGA | WATER SOURCE HEAT PUMPS
OMEGA-VSHPe.F-IOM-1912
29
www.omega-heatpump.com
Omega has a policy of continuous product improvement and reserves the right to change design and specifications without notice.
VSHPe UNIT START
-
UP SHEET
INSTALLATION INFORMATION
Job Name____________________________
City______________________Province/State_______________Postal/ZIP Code___________
OMEGA Unit Model #____________________________________________________________
OMEGA Unit Serial #____________________________________________________________
Unit Tag#__________________________
Technician___________________________Company_________________________________
Heating
Note: Room temperature must be min. 60
o
F
Riser Fluid Loop Temperature:
Entering Water Temperature (EWT):______F
Leaving Water Temperature (LWT): ______F
T = EWT
-
LWT = _________
o
F
Water Flow Rate (GPM):______
(units with optional balancing valve see name-
plate for GPM rating)
Air Temperature (Measure the difference in tem-
perature across air coil) for measuring sensible
capacity:
T = LAT
-
EAT
Sensible Capacity (Btuh) =
T x CFM x 1.08
Entering Air Temperature (EAT):______F
Leaving Air Temperature (LAT): ______F
T = _________
o
F
Sensible Capacity (Btuh) = _________
Fan Speed Used:
Low
Med
High
Compressor Amp:
________
Fan Amp:
________
Run Time For Test:
________
Cooling
Riser Fluid Loop Temperature:
Entering Water Temperature (EWT):______F
Leaving Water Temperature (LWT): ______F
T = LWT
-
EWT = _________
o
F
Water Flow Rate (GPM):______
(units with optional balancing valve see name-
plate for GPM rating)
Air Temperature (Measure the difference in tem-
perature across air coil) for measuring sensible
capacity:
T = EAT
-
LAT
Sensible Capacity (Btuh) =
T x CFM x 1.08
Entering Air Temperature (EAT):______F
Leaving Air Temperature (LAT): ______F
T = _________
o
F
Sensible Capacity (Btuh) = _________
Fan Speed Used:
Low
Med
High
Compressor Amp:
________
Fan Amp:
________
Run Time For Test:
________