10. MAINTENANCE GUIDE
Proper unit maintenance will result in optimal unit performance
and prevent potentially costly repairs or property damage. Turn
unit disconnect switch to off and turn unit off at circuit breaker/
fuse panel before starting maintenance procedure.
Do not operate unit without filters or during any
temporary construction that could clog the air filter
or air coil.
Do not use any cleaning solutions that contain acids
on the air
-
refrigerant coil or any refrigerant compo-
nents.
30 DAY MAINTENANCE
1.
Visually inspect filter monthly for dirt and clogging. Re-
place as required with a quality filter.
2.
Vacuum dust from unit air grilles and surrounding coil area
with soft bristle brush attachment as required.
3.
Filters with a rating higher than MERV 11 may need to
changed more regularly as they will reduce airflow as they
become dirty.
4.
Every month visually inspect unit for any signs of water
leaks, or water damage around floor or surrounding dry-
wall.
3 MONTH MAINTENANCE
1.
Remove ERV filters located at each ERV fan and wash
with water or mild soap.
2.
Inspect condensate drain every 3 months for signs of
stagnant water, microbial growth, and mineral buildup.
Clean drain pan with an appropriate cleaning solution as
required to prevent condensate hose blockages and mi-
crobial growth.
3.
Check valves and hoses for signs of leaks, cracking or
deterioration.
6 MONTH MAINTENANCE
1.
Remove ERV Core and wash with water or mild soap.
2.
Check condensate flow to ensure adequate drainage and
test for signs of impending blockages.
3.
Check that condensate alarm is operating correctly. Alarm
trips whenever water level rises above sensor threshold
and locks unit operation.
4.
Visually inspect the air coil for signs of dirt accumulation.
Use a mild detergent or coil
-
cleaning agent. DO NOT use
any cleaning solutions that contain an acid, including ace-
tic acid (vinegar). Damage to the air coil may occur result-
ing in possible refrigerant leaks.
ANNUAL MAINTENANCE
1.
Perform an annual maintenance inspection of the fan and
blower motor assembly. All units come with permanently
lubricated fan motors. DO NOT oil or lubricate fan motors.
Clean up any dirt or debris that may have accumulated.
2.
Visually inspect the electrical box annually for signs of
component damage due to overheating or poor electrical
contact.
3.
Completely clean the interior of the cabinet. Vacuum any
dust or debris.
REPLACEMENT FILTERS
Disposable 1
-
inch thick replacement filters, sizes listed below
and can be obtained from any HVAC parts supplier.
Factory provided filters are Merv 11Pleated filters rated be-
tween MERV 8 to MERV 11 are preferable as they will provide
optimal filtration. Higher rated filters (MERV 12, 13+) may re-
duce airflow and affect unit heating and cooling performance.
Verify that the unit can produce the desired airflow before in-
stalling high efficiency filters.
Table 7: Replacement Filter Sizes
VSHPe 030
VSHPe 040
VSHPe 050
VSHPe 060
VSHPe 080
VSHPe 100
VSHPe 120
20 x 25 x 1
14 x 25 x 1
Model
Replacement Filter
Size (in)
16 x 25 x 1