OMEGA-VSHP.G-IOM-2103
26
Figure 15
Acoustic Panel Furring Detail
—
Typ. 2x2 Framing Plan View
Figure 16
Acoustic Panel
—
Typ. 2x4 Framing Plan View
Notes:
1)Provide 2” from framing stud to cabinet. With optional 2-inch MERV 13 filter provide 3” from front of stud or min 1-1/2” from back
of stud to cabinet. With optional flange, provide gap min. 1/2” from stud to flange.
2) Return air panel should be centered in front of the unit return air opening.
3) With rear/side risers, allow for min. 6” typical clearance at the rear/side of the units.
4) For additional sound attenuation insulate the closet cavity with plenum rated acoustical insulation.
Optional: seal
with foil tape,
sheet metal or
duct board
0.625"
1)
Front of Cabinet to Front of Stud:
Min. 2"
Typ. 1/2" Drywall
Nom. 2x2 Studs Shown
(1-1/2" x 1-1/2")
Removable
Acoustic RA Grille
PLAN VIEW
VSHP CABINET &
ACOUSTIC RETURN AIR PANEL
Standard 1" Filter
Screws x 4
Rough-In Width
Acoustic
RA Panel Frame
Unit Cabinet to Back Wall:
No Risers = Min. 1/2"
W/ Risers = Min. 6" Typ.
Unit Cabinet to Left/Right Wall:
W/ Nom. 2"x2" Studs = Min. 1-1/2"
Optionally Seal RA Perimeter w/
Foil Tape or Duct Board
VSHP/VSHY CABINET
1)
Front of Cabinet to Front of Stud:
Min. 3"
Optional 2"
MERV 13 Filter
Optionally Seal RA Perimeter w/
Foil Tape or Duct Board
VSHP/VSHY CABINET