Troubleshooting Guide
28
4
2. Loose or broken wires:
Check each terminal connection for tightness. Move each wire
back and forth and note any changes in operation.
3. Too high a load resistance in the output current loop or too
low a current rating on the power supply:
a)
Measure the total resistance of each device (excluding the
transmitter and power supply) in the 20 mA loop, including
the resistance of the lead wires.