37 |
M 5 7 5 1
7.5
Digital Output Configuration
Two output signals are available which may be configured for ON/OFF, PWM, or SERVO outputs through the Output
Configuration registers (0x0124 and 0x0126). The remaining outputs are assigned as phantom devices which are
non-configurable. The highlighted entries show typical default configurations.
Digital Output Configuration
7
6
5
4
3
2
1
0
Output Configuration
Servo Range
1.0 – 2.0 0
0.5 – 2.5 1
Active State
LOW
0
HIGH
1
Rate
100 Hz
0 0 0
10 Hz
0 0 1
1 Hz
0 1 0
0.1 Hz
0 1 1
50 Hz
1 0 0
33 Hz
1 0 1
25 Hz
1 1 0
20 Hz
1 1 1
15
14
13
12
11 10
9
8
Output Type
Sensor Mapping
No Mapping
0
-
-
Sensor 0
1
0
0
Sensor 1
1
0
1
Sensor 2
1
1
0
Sensor 3
1
1
1
Mapping Enable
Not
Enabled
0
Enabled 1
Output Type
Null
0 0 0 0
ON/OFF
0 0 0 1
PWM
0 0 1 0
Servo
0 0 1 1
7.5.1 Rate
The Rate determines the repetition rate, or frequency, of the Digital Output. For On/Off outputs the rate
field is ignored.
7.5.1.1 PWM Rate
The SP-013 supports the following PWM frequencies:
PWM Rate
Name
Description
0
100 Hz
PWM signal has constant 100 Hertz frequency (10 msec repetition
rate) with 0 – 100 % duty cycle
1
10 Hz
PWM signal has constant 10 Hertz frequency (100 msec repetition
rate) with 0 – 100 % duty cycle
2
1 Hz
PWM signal has constant 1 Hertz frequency (1-second repetition
rate) with 0 – 100 % duty cycle
3
0.1 Hz
PWM signal has constant 0.1 Hertz frequency (10-second
repetition rate) with 0 – 100 % duty cycle