User’s Guide

 

SP-003 / SP-004

 

Omega Link Environmental Monitoring 

Smart Probe 

3” Bulkhead Housing

 

Содержание SP-003

Страница 1: ...TM 3 Tube Housing 5 Tube Housing User sGuide SP 003 SP 004 Omega Link Environmental Monitoring Smart Probe 3 Bulkhead Housing...

Страница 2: ...ves the right to alter specifications without notice omega com info omega com Omega Engineering Inc 800 Connecticut Ave Suite 5N01 Norwalk CT 06854 USA Toll Free 1 800 826 6342 USA Canada only Custome...

Страница 3: ...screte Input Output DIO 13 Setting DIO as an Input 14 Advanced Scaling Options 14 5 4 Output Configuration 15 Device Output Range Types 16 ON OFF Output Type 16 Pulse Width Modulation PWM Output Type...

Страница 4: ...Temperature Data Type Format 27 Dewpoint Temperature Configuration Byte 27 Dewpoint Temperature Device Byte 28 Dewpoint Temperature Parameters 28 Dewpoint Temperature User Calibration 28 IPSO Dewpoin...

Страница 5: ...5 M 5 7 4 8 SERVO Rate 36 Output Type 36 Active State 36 Mapping Enabled 36 Sensor Mapping 36...

Страница 6: ...it contains important information relating to safety and EMC Failure to follow all the safety precautions may result in injury and or damage to your equipment The following labels identify information...

Страница 7: ...P 0003 SP 004 Unit Quick Start Guide Additional Material Needed An Omega Link Smart Interface A Windows 7 8 9 10 or 11 OS PC or laptop with Omega s free SYNC configuration software A compatible Omega...

Страница 8: ...conds Repeatability 0 21 RH Barometric Pressure Accuracy Over Full Range 6 mbar from 300 to 1100 mbar Accuracy 25 C 4 mbar from 700 to 1100 mbar Dewpoint Calculated Accuracy 2 C Heat Index Calculated...

Страница 9: ...S M FM will need to be connected between the Smart Interface and Smart Probe Refer to the previous pin diagram and the wiring diagram below to connect the accessories 4 2 Bulkhead Mechanical Dimensio...

Страница 10: ...ct the device follow these instructions to manually connect it Step 1 Click on the icon located on the top left of the SYNC interface Step 2 Proceed through the Add Device Wizard and click End Device...

Страница 11: ...ortant The following parameters should NOT be changed These settings should NOT be changed unless the configuration has been done on the interface BaudRate Controls bits per second DataBits The number...

Страница 12: ...SP 004 2 add Dewpoint Humidex and Heat Index sensor readings in addition to temperature humidity and barometric pressure To access the dewpoint Humidex or Heat index sensor through SYNC click the Inp...

Страница 13: ...es the output circuitry The internal process drives the output control signal to turn on the output driver which will force the output low When the state of the DIO input signal is to be read the proc...

Страница 14: ...yed unit can be changed To apply a gain or offset to the input expand the Scaling menu and ensure that Apply Scaling is checked There the gain and offset values can be adjusted Both positive and negat...

Страница 15: ...ctive High or Active Low When configured as Active High the output conducts normally and becomes high impedance when activated When configured as Active Low the Open Drain output is high impedance nor...

Страница 16: ...has a constant 1 Hz frequency with 0 100 Duty Cycle 0 1 Hz Signal has a constant 0 1 Hz frequency with a 0 100 Duty Cycle Signal Type Active LOW When the output is active it is pulled to ground LOW Ac...

Страница 17: ...e icon will open the Define ON OFF Control dialog box as seen below The Enable Control checkbox enables the ON OFF control module If this box is unchecked the output will be disabled but the module wi...

Страница 18: ...clicking the icon in SYNC on the desired input signal found in the Input Tab Configure the Condition that triggers the alarm by selecting an option from the drop down such as Above or Below The Thres...

Страница 19: ...006 push the pairing button once on the IF 006 The LED status indicator will blink green indicating the device is in Pairing Mode Step 2 Quickly push the pairing button on the Omega Link Gateway The...

Страница 20: ...H Dewpoint D Temperature T Relative Humidity RH Barometric Pressure P and DIO Each enumerated Sensor has a Descriptor Base address location and a Sensor IPSO Configuration structure address location b...

Страница 21: ...its of measure Temperature Sensor Type Sensor Type SI Derived Units Measurement 0x01 o C Temperature Temperature Data Type Format Temperature Data Type Format 7 6 5 4 3 2 1 0 Smart Sensor Writeable Fa...

Страница 22: ...information Offset Name Value Description 0x00 Sensor Type 3303 Temperature o C 0x02 Precision 1 Provides reading of xxx y 0x04 Reset Min Max See below 0x08 Min Measured Minimum reading since last res...

Страница 23: ...3 2 1 0 Smart Sensor Writeable Factory Calibrate Data Type 0 0 0 0 6 Floating point Data Type The 4 bit Data Type field determines the type of data of the specific sensor Factory Calibrate The Factory...

Страница 24: ...e Humidity 0x02 Precision 1 Provides reading of xxx y 0x04 Reset Min Max See below 0x08 Min Measured Minimum reading since last reset 0x0c Max Measured Maximum reading since last reset 0x10 Min Range...

Страница 25: ...ure Data Type Format 7 6 5 4 3 2 1 0 Smart Sensor Writeable Factory Calibrate Data Type 0 0 0 0 6 Floating point Data Type The 4 bit Data Type field determines the type of data of the specific sensor...

Страница 26: ...x00 Sensor Type 3315 Barometric Pressure mbar 0x02 Precision 1 Provides reading of xxx y 0x04 Reset Min Max See below 0x08 Min Measured Minimum reading since last reset 0x0c Max Measured Maximum readi...

Страница 27: ...4 3 2 1 0 Smart Sensor Writeable Factory Calibrate Reserved Data Type 0 0 0 0 6 Floating point Data Type The 4 bit Data Type field determines the type of data of the specific sensor Factory Calibrate...

Страница 28: ...ption 0x00 Sensor Type 33123 Dewpoint Temperature C 0x02 Precision 0 Provides reading of xxx 0x04 Reset Min Max See below 0x08 Min Measured Minimum reading since last reset 0x0c Max Measured Maximum r...

Страница 29: ...f measure Apparent Heat Sensor Type Sensor Type SI Derived Units Measurement 0x3a o C Heat Index Apparent Heat 0x3b o C Humidex Apparent Heat Apparent Temperature Data Type Format Apparent Heat Data T...

Страница 30: ...e is not used Apparent Heat Temperature Parameters There are no user accessible parameters for the Apparent Heat sensor Apparent Heat User Calibration There are no Apparent Heat user calibration regis...

Страница 31: ...s 2 digital inputs which are hardwired to the Digital outputs The DIO inputs may be used to detect the state of external switches output off or to monitor the state of the outputs DIO Descriptor Offse...

Страница 32: ...Scaling If set the user defined Offset and Gain values will be used to adjust the sensor reading Result Raw Reading Gain Offset Assigned The Assigned bit will always read as 0 Available The Available...

Страница 33: ...set Min Max 15 14 13 12 11 10 9 8 0 0 Calibration Reset Calibration Status Calibration Mode Capture High Capture Low Calibration Start Setting the Reset Min Max bit to 1 will reset the Min Max values...

Страница 34: ...mapped the scaling values are used to transform the minimum input value to 0 and the maximum input value to 100 see Sensor Scaling Output Name Modbus Address I2C Address Size Description 0 Output 0 Va...

Страница 35: ...ensor Mapping No Mapping 0 Sensor 0 1 0 0 Sensor 1 1 0 1 Sensor 2 1 1 0 Sensor 3 1 1 1 Mapping Enable Not Enabled 0 Enabled 1 Output Type Null 0 0 0 0 ON OFF 0 0 0 1 PWM 0 0 1 0 Servo 0 0 1 1 Rate The...

Страница 36: ...Mapping Enabled The read only Mapping Enabled bit indicates that the output may be optionally directly mapped to a sensor input based on the Sensor Mapping field If the Mapping Enabled bit is clear no...

Страница 37: ...A if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to m...

Страница 38: ...s M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U...