Step One

SPECIFICATIONS

Range:

LVCN704: 2" to 4'
(5 cm to 1.2m)
LVCN709: 4" to 9.8'
(10 cm to 3m)
LVCN716: 4" to 16.4'
(10 cm to 5m)
LVCN126: 8" to 26.2'
(20 cm to 8m)

Repeatability:

0.25" (6 mm)

Adjustability:

Over entire range

Hysteresis:

LVCN704/709: 0.5" (1.2 cm)
(single set point)
LVCN716/726: 1" (2.5 cm)
(single set point)

Beam width:

LVCN704/709: 2" (5 cm) dia.
LVCN716/726: 3" (7.6 cm) dia.

Dead band:

LVCN704: 2" (5 cm)
LVCN709/716: 4" (10 cm)
LVCN726: 8" (20 cm)

LED indication:

Power, relay and echo status

Calibration:

Target, push button

Memory:

Non-volatile

Supply voltage:

AC: 95-250 VAC
DC: 12-28 VDC (Optional)

Consumption:

AC: 20 watts max.
DC: 100 mA @ 24 VDC (Optional) 

Contact type:

(3) SPDT relays

Contact rating:

60 VA

Contact logic:

Single point: alarm
Two point: latching or
out of bounds alarms
Duplex or Alternation:
(Relays 1 and 2 only)

Contact fail-safety:

De-energizes during echo signal loss

Process temp.:

F: -4° to 140°
C: -20° to 60°

Temp. comp.:

Automatic

Electronics temp.:

F: -40° to 160°
C: -40° to 71°

Pressure:

30 psi (2 bar) @ 25° C., derated @ 
1.667 psi (.113 bar) per °C. above
25° C.

Enclosure rating:

NEMA 4X (IP65)

Enclosure vent:

Water tight membrane

Encl. material:

PC/ABS FR

Trans. material:

PVDF Kynar®

Process mount:

LVCN704/709: 1" NPT (1" G)
LVCN716/726: 2" NPT (2" G) 

Mount. gasket:

Viton®

Conduit entrance:

Dual, 1/2" NPT

Classification:

General purpose

CE compliance:

EN 61326 EMC
[DC series only (DC powered)]

Handling Static-Sensitive Circuits/Devices:

When han-

dling the Ultrasonic switch, the technician should follow
these guidelines to reduce any possible electrostatic charge
build-up on the technicians body and the electronic part.

1. Always touch a known good ground source before handling the

part.  This should be repeated while handling the part and more
frequently after sitting down from a standing position, sliding
across the seat or walking a distance.

2. Avoid touching electrical terminals of the part unless making connections.

3. DO NOT open the unit cover until it is time to calibrate.

1.2"

(32 mm)

1.9" 

(49 mm)

3.9" 

(100 mm)

5.2"

 (133 mm)

2.4" 

(62 mm)

1" NPT

 (1" G)

0.75"

(19 mm)

LU75

LU72

2.5"

(63 mm)

4.5" 

(1

14 mm)

5.2"

 (133 mm)

3.0"

(76 mm)

2" NPT

(2" G)

1.7"

(44 mm)

4.1"

 (104 mm)

5.2"

 (133 mm)

3.8"

 (96 mm)

40

30

 

20

 10

 00

-40

-20

00

20

40

60

80

Acceptable

Range

Unacceptable

Range

Temperature/Pressure Derating

Operating Pressure (psi)

Temperature (C¡)

LVCN716
LVCN726

Enclosure (Side View)

LVCN704
LVCN709 

Enclosure (Side View)

LVCN700 Series

Enclosure (Top View)

All manuals and user guides at all-guides.com

Содержание LVCN700 Series

Страница 1: ...nder warranty and 3 Repair instructions and or specific problems relative to the product FOR NON WARRANTY REPAIRS consult OMEGA for current repair charges Have the following information available BEFO...

Страница 2: ...C ABS FR Trans material PVDF Kynar Process mount LVCN704 709 1 NPT 1 G LVCN716 726 2 NPT 2 G Mount gasket Viton Conduit entrance Dual 1 2 NPT Classification General purpose CE compliance EN 61326 EMC...

Страница 3: ...lease refer to the part number located on the switch label to verify the exact model con figuration which you have purchased User s Responsibility for Safety Omega manufactures a broad range of level...

Страница 4: ...nergize until the level reaches the de energize set point Alternation will automati cally fill or empty the tank with two pumps switching after each cycle PREPARATION A Supply Voltage The power supply...

Страница 5: ...pro gram the channel with new set points or leave it inactive PROGRAMMING Set Point Calibration Box Insert Table Target Wall Tape Distance Set Point Cal Run High Low Select RELAY 1 RELAY 2 RELAY 3 L1...

Страница 6: ...ramming High Set Point Distance Low Set Point Distance Energize Energize De energize Out of Bounds D Programming Automatic Fill After having powered the switch with the appropriate supply voltage ente...

Страница 7: ...ogramming Duplexing Pump Control After having powered the switch with the appropriate supply voltage entered the CAL mode selected relay channel 1 and erased any previously input set points follow the...

Страница 8: ...m start up Gasket Flange on Riser Height Inner Diameter Riser Bracket Stand Pipe Dead Band Ventilation Hole Operational Range Highest Liquid Level Lowest Liquid Level 2 3 Minimum Diameter Step Twelve...

Страница 9: ...or turbulence that may reduce or eliminate the acoustic signal strength Read the Maximum Applied Range Step 4 E and consider rein stalling the switch in a Stand Pipe Step 11 A 4 to dampen turbulence...

Страница 10: ...exing Control Operation Alternating Control Operation OPERATION Step Sixteen Relay X Energize De Energize Start Stop Automatic Empty Operation Automatic Fill Operation Out of Bounds Operation Relay X...

Отзывы: