28
ACTIVE SUBMENU:
Press
d
11)
Display flashes previous selection. Press
b
to scroll through
the available selections:
ABoV
Above,
BELo
Below,
HI.Lo
HI/Low and
BAND
Band. (Band is active if
_DEV
Deviation was
selected).
Press
d
12)
Display shows
STRD
stored message momentarily and then
advances to
A.P.oN
only if it was changed, otherwise press
a
to
advance to
A.P.oN
Alarm Enable/Disable at Power On Submenu.
Above
: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below:
Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low:
Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band:
Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.