21
KNOWN/UNKNOWN LOADS SUBMENU:
Press
d
8)
Display flashes previous selection of
ENBL
Enable or
DSBL
Disable.
Press
b
9)
Scroll though the available selection of
ENBL
or
DSBL
(flashing).
Press
d
10)
Display shows
STRD
stored message momentarily and then
advances to
L.PNT
Linearization Points Submenu.
If
ENBL
Known Loads scaling method was selected, calculate
the input values to the instrument based on the actual signal
being received. If
DSBL
Without Known Loads scaling method
was selected, calculate input values to the instrument based on
the transducer specification.
LINEARIZATION POINTS SUBMENU:
Press
d
11)
Display flashes previous selection of Linearization Points
Submenu.
Press
b
12)
Scroll though the available selections:
0002
,
0003
,
0004
,
0005
,
0006
,
0007
,
0008
,
0009
,
0010
- up to 10
Linearization Points can be selected. Default is
0002
.
If display flashes
NONE
, your instrument has only 2 linearization
points.
Press
d
13)
Display shows
STRD
stored message momentarily only, if a
change was made, otherwise press
a
to advance to the
FLTR
Filter Constant Submenu.
Linearization Points allow users to customize the Transducer curve.
FILTER CONSTANT SUBMENU:
Press
d
14)
Display flashes previous selection for Filter Constant.
Press
b
15)
Scroll though the available selections:
0001
,
0002
,
0004
,
0008
,
0016
,
0032
,
0064
,
0128
. - Default is
0004
Press
d
16)
Display shows
STRD
stored message momentarily only, if a
change was made, otherwise press
a
to advance to
IN.RD
Input/Reading Submenu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.