Modbus Register Definition for iDRX-ACC, iDRX-ACV, iDRX-RTD, and iDRX-TC
Reg. #
Read Function
Write Function
# of byte
1
Input Range
Input Range
1
2
Input/Output Config.
Input/Output Conf.
1
3
Decimal Point
Decimal Point
1
4
Filter Time Constant
Filter Time Constant
1
5
Reading/Output Scale
Not supported
3
6
Reading/Output Offset
Not supported
3
7
Comm. Parameters
Comm. Parameters
1
8
Comm. Bus Format
Comm. Bus Format
1
9
Comm. Data Format
Comm. Data Format
1
A
Comm. Device Addr.
Comm. Device Addr.
1
B
Comm. Recog. Char.
Comm. Recog. Addr.
1
C
Unit of measure
Not supported
3
D
Gate Time
Gate Time
1
E
Debounce Time
Debounce Time
1
F
Transmit Time
Transmit Time
2
10
Main Value
Hard Reset
3
11
Peak Value
Reset Peak
1
12
Valley Value
Reset Valley
1
13
Not Supported
L.S. bytes Output Scale
2
14
Not Supported
M.S. byte Output Scale
1
15
Not Supported
M.S. bytes Output Offset
2
16
Not Supported
L.S. byte Output Offset
1
Note:
1) Main, Peak, Valley value: 4 bytes will send from the unit
a. Highest byte always 00h.
b. 2nd Highest byte: (MSB is sign (1= negative, 0= positive), next 3 bits are number of
decimal points).
c.
Low nibble of second byte, and lowest 2 bytes are the value.
d. The decimal point register has to set to: 1, 2, 3, or 4.
2) Bus Format:
Bit 5 1/0 = Modbus/Newport
3) Output Scale/Offset Write:
Due to write single only, two write operation is needed to write scale/offset, and to make it
effective it needs to follow with Hard Reset command.
4) To configure to Newport protocol, set bit 5 of Bus Format to low and follow with Hard Reset
command.