Section 10.1 - Error indications
Readout at hardware error
Error search
Readout
Error cause
Test of internal CJC sensor
CJ.ER
CJC sensor defect or temperature
outside range
Checksum test of the configuration in FLASH
FL.ER
Error in FLASH
Check measurement of analogue output current
AO.ER
1) No load on the current output
(only S4...20/S20...4 mA)
Communications test DRSL-DISPLAY/DRST-UR
NO.CO
Connection error
Check that input signal matches input configuration
IN.ER
1) Error levels on input
Check that saved configuration in DRSL-DISPLAY matches device
TY.ER
Configuration is not DRST-UR
! Error indications in the display flash once per second. The help text explains the error.
1) The error is reset by switching off and then switching on the supply voltage to the device.
Error Indications