16
DRSL-DISPLAY/DRST-CM display readout
9
Display readout below min. / above max. (-1999, 9999):
Input
Range
Readout
Limit
All
All
-1999
Display readout <-1999
9999
Display readout >9999
Section 9.1 DRSL-DISPLAY/DRST-CM display readout
Readout at hardware error
Error search
Readout
Cause
Check measurement of analog output
AO.ER
No load on the current output (only S4...20 mA)*
Communications test between
DRSL-DISPLAY/DRST-CM and DRST-AC
NO.CO
Connection error
Configuration error
CO.ER
Default configuration is loaded
Configuration error
CO.ER
Invalid configuration**
Check that saved configuration in
DRSL-DISPLAY/DRST-CM matches device
TY.ER
Invalid type or rev. no.
Hardware error
RA.ER
RAM error*
Hardware error
AD.ER
A/D converter error*
Hardware error
AO.SU
Analog output supply error*
Hardware error
EF.ER
External flash error*
Hardware error
IF.ER
Internal flash error*
!
All error indications in the display flash once per second. The help text explains the error. If the error is an
input loop error, the display backlight flashes as well - this is acknowledged (stopped) by pushing the 3
button.
*
Error is acknowledged by either stepping through the basic setup, or by resetting the device power.
Some types of errors can only be acknowledged by resetting the device power.
** Error is acknowledged by stepping through the basic setup.
Configurable input error detection - readout (IN.ER):
Input
Range
Readout
Limit
CURR
All
IN.ER
See table on page 14
VOLT
All
IN.ER
See table on page 14
Display readout of input error detection and signal ”outside range”