5-2
Setting Scaling
Setting
SRp1, p2, p3, p4, p5, p6, p7, p8, p9<terminator>
p1
Channel number (001 to 030)
Conputation channel number (A01 to A30)
p2SCL
p3
Type of input
VOLT DC voltage
TC
Thermocouple
RTD
Resistance temperature detector
DI
Contact
mA
DC current
p4
Measurement range
p5
Left value of span
p6
Right value of span
p7
Left value of scale (-30000 to 30000)
p8
Right value of scale (-30000 to 30000)
p9
Decimal point position of scale (0 to 4)
Example
Change channel 02 of subunit 0 to an input in which 1
V is converted to 0.00 and 5 V to 100.00.
SR002, SCL, VOLT, 6V, 1000, 5000, 0, 10000, 2
Comments
• For the p4 measurement range, see the range
parameter table on Pages 4-7 and 4-8.
• For the p5 and p6 setting spans, set them in the ranges
shown in the setting range on Pages 4-7 and 4-8.
• For p5 and p6 setting values, enter them within 6
digits excluding the decimal point.
• Select either to set all three parameters, p7, p8 and
p9, or to omit them all.
SN
Sets the scaling unit.
Mode
Operation mode
Setting
SNp1, p2<terminator>
p1
Channel number (001 to 030)
Computation channel number (A01 to A30)
p2Unit character string (up to 6 characters)
Example
Set the scaling unit for channel 01 slot 0 to ABCDEF.
SN001, ABCDEF
Comments
• For a character string that can be used as units, see
the characters in Section 4.6, “ASCII Code Table.”
However, note that a semi-colon “;” cannot be used.
• The optional computation channel number for a
stand-alone model is A01 to A30.
5.1 Setting the Input
Содержание DR130 SERIES
Страница 1: ...http www omega com e mail info omega com User sGuide DR130 DR230 DR240 SERIES Communication Interface ...
Страница 39: ...4 9 Command Format 4 4 5 Input Range Parameter This page intentionally left blank ...
Страница 40: ...4 10 4 5 Input Range Parameter This page intentionally left blank ...
Страница 56: ...5 15 Commands 5 This page intentionally left blank 5 5 Other Settings ...
Страница 71: ...6 9 Output Format 6 This page intentionally left blank ...