Configuring The Meter
38
Note
☞
38
4.11 SELECTING PROPORTIONAL BAND
P.BND
Proportional Band
P.BND
is not active unless your meter has analog output and relay
capabilities. The menu will display whether analog output is present or not.
•
A proportional controller's output is linearly proportional to the change of the
error signal, whenever the signal is within 2 prescribed values (Proportional
Band).
•
There are three (3) points of interest on the proportional controller transfer
curve.
•
The first is the magnitude of the error signal that drives the controller to
“full on” (e.g. 20 mA out for 4-20 mA).
Figure 4-2. Controller Output
•
The second point of interest is the magnitude of the error signal that drives
the controller output to “full off” (e.g. 4 mA out on 4-20 mA). These two (2)
points need not be equally spaced on either side of the zero error point.
•
The third is the factor "Offset" and it is the output value of the
controller which causes zero error.
The above example illustrates the parameters for the 4-20 mA analog out,
likewise, analog voltage output will have these (3) points of interest.
PROPORTIONAL BAND
MIN
0%
100%
ERROR=READING SETPOINT
OFFSET
CONTROLLER OUTPUT
MAX
4mA
20mA
Zero error
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание DP25B-E
Страница 11: ...viii Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 70: ...59 NOTES Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 71: ...60 NOTES Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...