2.4.2 Thermocouple
The figure below shows the wiring hookup for any thermocouple type. For
example, for Type K hookup, connect the yellow wire to the "2" terminal and the
red wire to the "1(-)" terminal.
When configuring your controller, select Thermocouple and Thermocouple
Type in the Input Type menu (see Part 3).
Figure 2.6 Thermocouple Wiring Hookup
If the input wires of the meter get disconnected or broken, it will display
+OPN
“Input (+) Open” message. For safety purpose you may want to set
up your alarm to be triggered when input is open. Be sure to set your
Alarm correctly (see Alarm 1 & 2 chapters for details).
TYPE
Input Connector
Jacket (external insulation)
Terminal 1 (-)
Terminal 2 (+)
Extension
Grade
J
Red
White
dark-Brown
Black
K
Red
Yellow
dark-Brown
Yellow
T
Red
Blue
dark-Brown
Blue
E
Red
Purple
dark-Brown
Purple
N
Red
Orange
dark-Brown
Brown
R
Red
Black
-
Green
S
Red
Black
-
Green
B
Red
Gray
-
Black
Table 2.5 TC Wire Color Chart