13
_______________________________________________________
Process variable offset
±10% FS
_______________________________________________________
Setpoint variable offset
±50% FS
_______________________________________________________
Input filter
0-900.0 sec, setting in 0.1 sec steps
(primary lagging filter)
_______________________________________________________
Noise rejection ratio
Normal mode noise (50/60Hz): 50dB or more
Common mode noise (50/60Hz): 140dB or more
_______________________________________________________
POWER FAILURE PROTECTION
_______________________________________________________
Memory protection:
Non-volatile memory. Parameter values
remain unchanged with disruption of power.
Ramp/soak function has to be re-initiated.
_______________________________________________________
OPERATING AND STORAGE CONDITIONS
_______________________________________________________
Operating temperature
-10 to 50°C (14 to 122°F)
_______________________________________________________
Operating humidity
Less than 90% RH (non-condensing)
_______________________________________________________
Storage temperature
-20 to 60°C (-4 to 140°F)
_______________________________________________________
ADDITIONAL FUNCTIONS
_______________________________________________________
8-segment ramp-soak:
4 ramp/4 soak with 16 different modes
Setpoint setting: 0-100% FS
Ramp/soak period: 0-99 hrs 59 mins
_______________________________________________________
Parameter mask:
Parameters can be masked from being displayed
_______________________________________________________
Self-diagnosis:
Watchdog timer monitors program error
_______________________________________________________