6
Scb
Input Shift
Parameter Scb is used to make input shift to
compensate the error produced by sensor or input
signal itself.
PV-after-compensation=
PV-before-compen Scb.
-199~
+400
0
FILt
PV input filter
The value of FILt will determine the ability of
filtering noise.
When a large value is set, the measurement input
is stabilized but the response speed is slow.
Generally, if great interference exists, then you
can increase parameter “FILt” gradually to make
momentary fluctuation of measured value less
than 2 to 5.
When the meter of the instrument is being
examined at laboratory, “FILt” should be set to 0
or 1 to short the response time.
0~40 1
Fru
Selection of power
frequency and
temperature scale
50C: 50Hz,
℃
50F: 50Hz,
℉
60C: 60Hz,
℃
60F: 60Hz,
℉
50C, 50F,
60C, 60F
50C
SPL
Low limit of SV
-999~
3000
0
SPH
Upper limit of SV
-999~
3000
400