Parameter List (only relevant parameters shown):
PAR#: Parameter: Range/Units:
00
Process Temp.
Input determined
01
Setpoint
Input determined
19
Baud Selection
bAUd
Baud Selections:
Code:
Baud:
Parity: Data Bits: Stop Bits:
3.o.7 300 odd 7 2
6.o.7 600 odd 7 2
12.o.7
1200
odd
7
2 (factory default settings)
24.o.7 1200 odd 7
2
3.n.8 300 no 8 1
6.n.8 600 no 8 1
12.n.8 1200 no 8
1
24.n.8 2400 no 8
1
General Message Format:
#[controller id][command][parameter number]<new value><units>[CR/LF]
Definitions:
# - This character initiates an “escape sequence” that the controller will
recognize.
[controller id] – Up to 2 numeric characters, “00” to “99” (factory default=”01”)
[command] – 1 character, upper case or lower case
“R” – To read a parameter from the controller
“M” – To temporarily modify a controller parameter (lost upon shutdown)
“E” – To modify a controller parameter in non-volatile mem. (saved even
after shutdown)
[parameter #] – Up to 2 numeric characters, “00” to “99”
<new value> - This control word is used only when entering or modifying a
parameter.
Up to 6 characters may be entered. The first character can be a space, a “+”,
or a “-”. The next 4 characters are for entering the new value parameter value.
Be sure to use the exact same field format as is currently being used. (i.e. if the
BB701
4
4-2