Omega Engineering PSW32 SERIES Скачать руководство пользователя страница 6

Switching Characteristic Graphs

Signal “on” with 

rising

pressure 

Setting SP* > RP**

Explanation:

When the switching point (SP) is adjusted 

HIGHER

than the reset point (RP), then the switching output will be “normally off”. 

When the switching point (SP) is adjusted 

LOWER

than the reset point (RP), then the switching output will be “normally on”.

p

SP

RP

t

t

U

Signal “on” with 

falling

pressure 

Setting SP < RP

Signal “off” with 

rising

pressure 

Setting RP > SP

p

RP

SP

t

t

U

p

RP

SP

U

A

t

t

Signal “off” with 

falling

pressure 

Setting RP < SP

p

SP

RP

U

A

t

t

* SP  = Switching point

**RP  = Reset point

Pressure display

Switching 
function graph

Switching output LED

Raise switching
or reset point button

Lower switching
or reset point button

Reset point button

 Switching point button

Position of operating elements

Cod

Meaning

Requested code or code programming

CLC

Clear code

Deletion of current code

txx

Delay time

Setting of filter time constant

(Buffering time)

xx = Switching output delay
xx    {03, 06, 12, 24, 50} in ms and
xx    {O.1, 0.2, O.4} in s.

OFS

Offset

Request for offset adjustment using 

and 

buttons

SC.H

Shor t-circuit high

Shor t-circuit monitoring activated

U. LO 

Voltage low

Voltage monitoring activated

OFF

Off

Shor t-circuit or voltage monitoring deactivated

Std

Standard mode

Standard mode activated

HYS

Hysteresis mode

Hysteresis mode activated

FEn

Window mode

Window mode activated

U-C

Voltage calibration

Voltage output selected

I-C

Current calibration

Current output selected

Display

Meaning

Cause / Remedy

SC.H

Shor t-circuit high Shor t-circuit between output and power supply. Check wiring. 

If the switching line from the load (e.g. electrical control 
device, PLC or similar) is being held at an open-circuit 
potential of > 3V, or if several pressure switches are being 
operated in parallel, this function should be switched off.
Disconnection: 

during display test, then adjust with 

or 

.

U.Lo

Voltage low

Power supply voltage too low (<17V).
Check power supply: Load may be too large.
Disconnection: 

during display test, then adjust with 

or 

.

E

R R O R

M

E S S A G E S

Display of hardware errors or malfunctions

Display of hardware errors or malfunctions (can be switched off)

Messages generated by calling SETUP functions

Display

Meaning

Cause / Remedy

O.Er

Output error

Error at switching output: Circuit-breaker defective, feedback loop 
to processor open circuit. Repair necessary.

E.Er

E2PROM error

E2PROM module defective or connection to processor faulty. 
Repair necessary.

I.Er

Initialization error

Checksum of initialization data incorrect. Remedy: Call up any 
SETUP function and acknowledge the setting with SP. 
This error message is caused by a data error. All setup values 
should therefore be checked and corrected if necessary.

C.Er

Calibration error

Checksum of calibration data incorrect. Recalibration necessary.

SC.L

Short-circuit low

Short-circuit between output and ground. Check wiring: 
Power supply may be too weak for connected load (leading 
to collapse of voltage, particularly with loads with a high switch-on 
current such as incandescent lamps or capacitances).

UFL

Underflow

The applied pressure is below the measuring range: 
Increase pressure until it is within the measuring range.

OFL

Overflow

The applied pressure is above the measuring range: 
Decrease pressure until it is within the measuring range.

Содержание PSW32 SERIES

Страница 1: ...User s Guide www omega com e mail info omega com PSW32 SERIES ELECTRONIC PRESSURE SWITCH FOR HYDRAULIC APPLICATIONS ...

Страница 2: ...p 0800 1 66342 e mail czech omega com France 9 rue Denis Papin 78190 Trappes Tel 33 0 130 621 400 FAX 33 0 130 699 120 Toll Free in France 0800 4 06342 e mail france omega com Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany Tel 49 0 7056 3017 FAX 49 0 7056 8540 Toll Free in Germany 0800 TC OMEGA e mail germany omega com United Kingdom One Omega Drive River Bend Technology Centre ISO...

Страница 3: ...100 of FS Value Linearity 0 5 of FS 1 digit Electrical Connector Without Analog Output DIN 43650 Table A with Removable Cable Plug Adapter With Analog Output DIN 43651 7 Pin Circular Connector FEATURES Real time LED Status Display of Pressure Adjustable Hysteresis Off line Calibration Fast Accurate Response Extensive Service Life Analog Output Optional APPLICATION IIdeal for Control of Air Water G...

Страница 4: ... RP Load 1 24V 3 Uout Imax 1A 2 0V PE I Micro Controller SP RP p E2 PROM SP RP Load 1 73 44 1 57 40 1 57 40 47 12 59 15 A A Ø 12 3 94 24 1 4 18 NPT 22 5 5 22 5 5 View on A M5 35 9 45 11 5 79 20 Mounting Plates Included 1 4 NPT Pressure Port 304 Stainless Steel All dimensions in inches mm PART NUMBER IDENTIFICATION ELECTRICAL PARAMETERS Electrical connection DIN 43650 Table A without analog output ...

Страница 5: ...ad of the reset point this value can be selected as desired In order to set a hysteresis value the two buttons SP and must be pressed simultaneously before the power supply is switched on Release these buttons again after the power supply has been switched on and the display test has run The display will then show the operating mode The cursor buttons can now be used to change the operating mode u...

Страница 6: ...d power supply Check wiring If the switching line from the load e g electrical control device PLC or similar is being held at an open circuit potential of 3V or if several pressure switches are being operated in parallel this function should be switched off Disconnection during display test then adjust with or U Lo Voltage low Power supply voltage too low 17V Check power supply Load may be too lar...

Страница 7: ...wise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequen tial incidental or special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical appli cations or used on humans Sh...

Страница 8: ...IVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industrial pH Conductivity Equipment DATA ACQUISITION M U Data Acquisition Engineering Software M U Communications Based Acquisition Systems M U Plug in Cards for Apple IBM Compatibles M U Recorders Printers Plotters HEATERS M U Heating Cable Cartridge Strip Heaters M U Immer...

Отзывы: