List of functions: (xxxx = 125% f. s.)
Dialog item
Value
Description
MENU
-1...9999
Primary display, e.g. the value selected in the DISP menu appears
DISP
.....
Display value which should be permanently in the display:
act
actually measured value
sp1
switching point SP1
sp2
switching point SP2
max maximum peak value
min minimum peak value
ACT.
-1...9999
Display of actually measured value in bar
UNIT
bar
psi
psi
HPa
mbar
Fixing the unit
bar = bar
The unit is shown in the display appr.
psi x = psi x 10
every 30 sec. for appr. 5 sec.
psi =
psi
HPa =
Hekto-Pascal
mbar =
millibar
SP.1
.....
none switching output deactivated
wind window technology
stnd standard evaluation SP2
erro error output
ON-1
-1 ... xxxx
Switch-on point for SP1; if the ON value is smaller than the OFF
value the switching point evaluation is falling
OFF-1
-1 ... xxxx
Switch-off point for SP1
DLY1
0,0s...9,9s
Switch-on / switch-off delay for SP1 in seconds
INV-1
.....
Inversion of switching output SP1
hlfs
high-level-fail-save (normally open function)
Ilfs low-level-fail-save (normally closed function)
SP.2
.....
none switching output deactivated
wind window technology
stnd standard evaluation SP2
erro error output
ON-2
-1 ... xxxx
Switch-on point for SP2;
if the ON value is smaller than the OFF value
the switching point evaluation is falling
OFF-2
-1 ... xxxx
Switch-off point for SP2
DLY2
0,0s...9,9s
Switch-on / switch-off delay for SP2 in seconds
INV-2
-----
Inversion of switching output SP2
hlfs
high-level-fail-save (normally open function)
Ilfs low-level-fail-save (normally closed function)
MAX
-1 ... xxxx
Display of peak value „Max“ (xxxx: = max. 125 % f. s.)
CLRH
-----
Delete the maximum value memory
----- no
deletion
clr delete
value