5.4.3 RDC 2 MODBUS communication
ADDRESS NAME
TYPE
VARIABLE X
UNIT
40013
ADDRESS
RDWR
Address = X
40014
Service Time
R_ONLY
Service Time = X
day
40015
No. of alarms in last 24h
R_ONLY
Alarm 24 H Number= X
40016
No. of alarms since service
R_ONLY
Total Alarms = X
40017
Days Between Maintenance
R_ONLY
Days after Service = X
40018
Output Compressor Status
R_ONLY
0= Comp. OFF 1= Comp. ON
40019
Output Fan Status
R_ONLY
0= Fan OFF 1= Fan ON
40020
Output Drain Status
R_ONLY
0= Drain OFF 1= Drain ON
40021
Output Alarm Status
R_ONLY
0= Alarm OFF 1= Alarm ON
40022
T_Dew
R_ONLY
T_Dew = (X-200)/10
°C
40023
T_Comp
R_ONLY
T_Comp = (X-200)/10
°C
40024
T_Cond
R_ONLY
T_Cond = (X-200)/10
°C
40025
P_Cond
R_ONLY
P_Cond = X/10
Bar
40026
Digital Input status
R_ONLY
0= contact open 1 = contact close
40027
Buttons
R_ONLY
0= no switches 1= SET
2=UP 3= SET & UP
4= DOWN 5= SET & DOWN
6= UP & DOWN
7= SET & UP & DOWN
40028
Alarm CLn Status
R_ONLY
0=no alarm 1 = alarm active
40029
Alarm Lt Status
R_ONLY
0=no alarm 1 = alarm active
40030
Alarm Ht status
R_ONLY
0=no alarm 1 = alarm active
40031
Allarm PF1 Status
R_ONLY
0=no alarm 1 = alarm active
40032
Alarm PF2
R_ONLY
0=no alarm 1 = alarm active
40033
Alarm PF3
R_ONLY
0=no alarm 1 = alarm active
40034
Controller Status
R_ONLY
0= STANDBY 1=NORMAL
OPERATION 2=PROGRAMMING
MODE 3=ALARM MODE
4= TESTING MODE
Содержание RDT Series
Страница 29: ...29 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation...
Страница 30: ...30...
Страница 31: ...31 17 Drawings of RDT refrigeration air dryers RDT 20 100...
Страница 32: ...32 RDT 140 235...
Страница 33: ...33 RDT 300 480...
Страница 34: ...34 RDT 600 950...
Страница 35: ...35 RDT 1150 1900...
Страница 36: ...36 18 Electro schemes of RDT refrigeration air dryer RDT 20 180...
Страница 37: ...37 RDT 235 600...
Страница 38: ...38 RDT 750 1900...