CORRECTION FACTORS
To calculate the correct capacity of a given dryer based on actual operating conditions, multiply the nominal
inlet flow by the appropriate correction factor(s). CORRECTED CAPACITY = NOMINAL FLOW CAPACITY x C
OP
x
C
AT
x C
IN
x C
DP
OPERATING PRESSURE
[bar]
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
[psi]
29
44
58
72
87
100
115
130
145
160
174
189
203
218
232
C
OP
0,39
0,60
0,77
0,86
0,93
1,00
1,05
1,10
1,14
1,18
1,21
1,2
1,27
1,30
1,32
DEW POINT
°C
3
5
7
10
°F
37,4
41
44,6
50
C
DP
1
1,10
1,21
1,39
INLET TEMPERATURE AMBIENT TEMPERATURE
°C
≤25
30
35
40
45
50
55
°C
≤25
30
35
40
45
°F
77
86
95
104
113
122
131
°F
77
86
95
104
113
C
IN
1,2
1,12
1
0,83
0,69
0,59
0,5
C
AT
1
0,96
0,9
0,82
0,72
Содержание RDT Series
Страница 29: ...29 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation...
Страница 30: ...30...
Страница 31: ...31 17 Drawings of RDT refrigeration air dryers RDT 20 100...
Страница 32: ...32 RDT 140 235...
Страница 33: ...33 RDT 300 480...
Страница 34: ...34 RDT 600 950...
Страница 35: ...35 RDT 1150 1900...
Страница 36: ...36 18 Electro schemes of RDT refrigeration air dryer RDT 20 180...
Страница 37: ...37 RDT 235 600...
Страница 38: ...38 RDT 750 1900...