luminaire will change between maintained or no-
maintained mode. The change is recorded
permanently in it’s memory.
Indication LED status (with connected mains
power supply).
AC
Charge
On:
Good charge current.
Οff:
No battery (No charging current or
disconnected battery).
Lamp fault
Οn:
faulty LED strip (must be
checked by an authorized personel).
Off:
Good LED strip.
Fault
Ο
ff
:
Battery OK.
Blink
(
With
AC Charge LED
ON
): Autonomy or
low battery problem
(the battery must be replaced).
Blink
(
With
AC Charge LED
Off):
No charging current or disconnected battery
.
TEST
BUTTON
CHARGE
LED
FAULT
LED
LAMP
FAULT
LED
INDICATION LEDs
ELECTRICAL CONNECTIONS
1
2
3
4
Dismantle the luminaire by pushing the lock/unlock button
and slide the luminaire to the right and pull it down.
Pass thru the cables from the entry hole and connect them
as shown in the picture.
Place upwards the luminaire and slide it to the left. The
lock/unlock button appears indicating that the luminaire is
securely installed.
Power on the device
.
SURFACE MOUNTING ON A WALL (single sided)
Install the included bracket on the wall (page 3) and
perform the respective steps of the electrical connections.
CEILING INSTALLATION
Install the mounting base on the ceiling (page 3) and
perform the respective steps of the electrical connections.
NOTE!!
After finishing the installation you must power the luminaire
at least for 24 hours for battery charging to perform the
named autonomy.
L
N
Cable
entry
hole
Gnd
1
2
Installing the
luminaire
to the base
3
INSTALLATION INSTRUCTIONS
General
:
1. Operations for installation, maintainance or testing must be done by authorized personel only
.
2.
The device must be connected to the mains power supply thru a fuse dependent by the total
amount of the line’s power load
.
3.
In case of inactive use for a period greater than 2 months, disconnect the battery by pulling out
the battery’s connector.
4.
I s not allowed to discard batteries in to common trash bins, they must be discarded
t i
only
in battery recycling points. Do not incinerate.
922504461_09_002