Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
o
These luminaires are used indoors
(
ta 40 C
)
where emergency light is needed. Each
luminaire must be permanently connected to
mains power supply
.
In normal operation the
power
indicator lights and the
charge
indicator
blinks to show that the batteries are in charging
condition. In case of a mains power supply
failure the
power
and the
charge
indicators
turns off and the luminaire will light the spot
lamps automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions
ο
n page 2.
OPERATION
When the device is powered from the mains
,
th
e
charge
indicator
blinks and
confirms
the
charg
ing of
the batter
ies
.
When the batteries
are charged, it lights constantly.
If
it does
not
li
gh
t, probably, the batter
ies are
disconnected. If
it does
not li
gh
t and the batter
ies
are
connected, then contact the technician.
As long
as the charge indicator blinks, the batteries of
the luminaire are charging and in this period,
any autonomy test must be avoided. When the
charging circle is complete, the indicator lights
continuously (it can be used as an indication of
a power interruption). The batteries charging is
done by a 3 stages technological advanced
procedure, to ensure the appropriate and full
charging of the batteries.
The
power
indicator
confirms
the
proper connection to the
mains
. The
TEST
butto
n, has a dual use. If pressed
instantlly
while the device is
connected to the
mains
,
the
device
simulates
the
power
interruption
,
by
lighting
the
lamps for
3
''. In this
way
,
we can control the driver circuit of
the
lamps
and
the
lamps as indicated in paragraph
3
in
the text
below.
Dimming option
When the voltage is interrupted, with
corresponding press
ing
s of the button,
we ca
n
choose
the illumination of 100%, 50%, 33%
or
turned off
, either to increase the autonomy time or
not to consume
the
battery power unnecessarily.
This option is canceled when the network is
restored.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only
.
2.
The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line’s power load
.
3.
It is sugested to check every month the
indication LED for battery charging, and by
pushing instantly the TEST button to check the
emergency cirquit and the lamps. If the luminaire
does not light
4.
It is sugested to check every 6 months the
minimum autononous duration by disconnecting
the mains power supply
.
Count the time that the
lamps light and in case of less time than the
minimum autonomous duration the batteries
must be replaced. If the measured time is
considerably less than the minimum autonomous
contact the installer.
Page
1
from
2
``POWER LIGHT`` SERIES FOR NON-MAINTAINED EMERGENCY LUMINAIRES
923029009_09_005
Bayblend FR3010
,
transparent
polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY
(
Pb
)
CHARGING TIME
INDICATIONS
-
CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
<24h
Power indicator, battery charge indicator, TEST button
From overcharge and deep discharge
IP 42
0 to 40 C
o
Up to 95%
3 years
(1
year for the battery
)
White power LEDs
White LEDs
White LEDs
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
302x94x330mm
GRL-2
1
GRL-2
1
/H/90 GRL-2
1
/H/180
GRL-29
220-240V AC/50-60Hz
90 min
180 min
6V/4Ah
12V/7Ah
12V/7Ah
2x12V/7Ah
660lm
200
0lm
1
260lm
3.
5
W / 10VA
12W / 16VA
1965gr.
6300gr.
35
60gr.
4100gr.
High Quality European based Manufacturers