background image

 

 

 
 
01 

– 10 - 2013

 

 

980108003-09-003 

 

The JA-81F wireless keypad 

 

The JA-81F is a component of OASiS alarm system and is designed to control 
and  program  the  system.  It  has  a  built-in  proximity  access  card  reader  and 
allows the wiring up of a separate door detector. The battery-powered keypad 
communicates wirelessly using OASiS protocol. 

 

 

Installation 

 

Installation shall only be undertaken by technicians holding a certificate 

issued  by  an  authorized  distributor.  The  keypad  is  for  indoor  installation 
only, typically by the main entrance door. Avoid locating it close to metal 
objects which could shield radio communication. 

1. 

Open the keypad housing 

(by pressing the tab on the bottom) and 

disconnect the inter-housing connection cable inside (by pulling the 
connector from the board) 

2. 

Install the rear housing 

to the desired location 

3. 

Install the external hard-wired detector 

(if required)

 

and route its 

cable through the rear housing  

4. 

Enroll  the  keypad  to  the  control  panel 

(see  the  control  panel 

installation manual) as follows: 

  Enter  enrollment  mode  in  the  control  panel  (if  the  system  does 

not  have  a  keypad  already,  briefly  short  the  reset  link  on  the 
control  panel  main  board,  or  if  a  keypad  is  present,  then  press 
key 1 in service mode).  

  Install the battery into the keypad to trigger enrollment.  
  Exit enrollment mode by pressing the 

#

 key. 

5. 

Connect  the  inter-housing  cable

  to  the  board.  If  a  door  detector 

and an external AC adaptor are used, then connect their cables too.  
Attach the keypad to the rear housing. 

6. 

Instructions  on  how  to  use  the  keypad  can  be  found  in  the  control 
panel operating manual. 

7. 

 

 

Installing a door detector 

 

It is possible to wire up  a detector(s) to the keypad. The IN input terminal is 

triggered when disconnected from GND. The control panel’s natural reaction 
to  the  IN  input  being  triggered  is  a  delayed  intruder  alarm  linked  to  the 
keypad‘s  address.  If  desired,  another  reaction  can  be  programmed  in  the 
control  panel.  The  IN  input  can  indicate  a  door  being  permanently  open 
(status reaction). If the IN input is never used then it must be shorted to GND. 

 

Note:  The  lifetime  of 

the  battery  is  reduced 
proportionally to how 
frequently 

the 

door 

detector 

is 

triggered 

and  how  often  and  how 
long 

the 

keypad 

is 

battery-powered. 
 
 

 
 

 

Keypad sleep mode 

When battery-powered, the keypad saves energy by turning itself off when the 

cover is closed or automatically  after 20 seconds of inactivity  (15 minutes in 
service mode). 

The keypad is woken up by

: opening the keypad‘s flip cover, 

pressing any key, or triggering the wired door detector. 

Recommendation:

 

install the keypad with the door detector wired to its 

IN terminal

. The door detector will always turn the keypad on when the door 

is opened and the keypad can also indicate the entrance delay and be ready 
to read access cards. You will also save money on a wireless door detector. 

Note:

 If the keypad unit is powered by an AC adaptor there is no sleep mode, 

but 3 minutes after setting the system, status indication stops.  If desired, the 
system setting/unsetting status can be programmed in the control panel to be 
permanently indicate by the keypad.

 

Optional AC adapter 

If the keypad is powered by an AC adapter (model: Jablotron DE01-12 for 

terminals: +U and GND), it will not turn off after 20 seconds of inactivity. If 
the adapter is used, batteries should still be installed. Only turn on the AC 
adapter after the keypad unit has been powered up by batteries and the 
two halves of the housing are back together.

 

 

 

 

Keypad menu 

– language selection and door bell function 

If  the    key  is  kept  pressed  during  battery  connection  the  internal  keypad 

menu will be displayed allowing the selection of the 

desired language

. Using 

the arrows choose your language and confirm selection by the   key. 

In  this  menu  the 

door  bell  function

  can  also  be  enabled  or  disabled  (if 

enabled the keypad makes a sound when its IN input is triggered). 

Notes: 

 The menu can be displayed even if the keypad has not been enrolled to 

the control panel.  

 If  you  wish  to  display  the  menu  on  a  keypad  which  already  has  its 

battery installed, disconnect and reconnect the batteries first. 

 Each  keypad  has  its  own  menu,  i.e.  each  keypad  in  the  system  can 

have its own unique settings. 

 The keypad keeps its settings even if its power is disconnected (settings 

can only be altered via the keypad menu).  

 

 

Testing keypad communication  

In service mode, the control panel allows the keypad’s radio signal to be 
checked,  including  signal  strength  measurement.  To  test  the  keypad 
signal, trigger either its IN input or its tamper sensor. 

Note:

  the  control  panel  measures  the  strength  of  the  signal  transmitted 

by the keypad. It is impossible to measure the signal strength received by 
the keypad from the control panel. If the keypad has lost communication 
with  the  control  panel  (e.g.  if  the  control  panel  is  damaged)  it  would 
display  a  communication  error.  If  you  re-power  a  control  panel  which 
previously worked with a keypad, and the keypad does not function, then 
we recommend disconnecting and re-connecting the keypad batteries. 

 

 

Disabling the tamper sensor 

To  disable  the  tamper  sensor,  short  out  the  jumper  in  the  keypad  unit 
close to the tamper sensor (equipped with a spring). This is useful when 
carrying  the  keypad  unit  around  while  servicing  the  system.  During 
normal use of the system this jumper 

must remain open circuited

 

Keypad text editing  

There  are  two  kinds  of  text:  device  and  code  names  (displayed  on  the 
second line after the address number) and other system text. 

  The names can be edited via the keypad after pressing and holding the 

?

  key  in  service  mode 

–  see  the  control  panel  installation  manual.  The 

edited text is only stored in the keypad unit used for editing. 
  The  most  convenient  way  to  edit  text  is  to  use  a  PC  running 

OLink

 

software

.  To  transfer  edited  text  from  a  PC  to  the  keypad,  the  keypad 

(with  its  batteries  installed)  has to  be  connected  to the  OASiS system‘s 
digital  bus  (i.e.  one  cable  from  the  keypad  to  the  control  panel,  and 
another  cable  from  the  control  panel  to  the  PC).  If  there  are  multiple 
keypads,  they  can  all  be  connected  together  (via  the  digital  bus)  while 
transferring  edited  text  from  the  PC,  or  you  can  transfer  text  to  each 
keypad, one at a time. We recommend using a digital bus splitter (model 
BS-

84). OLink software also allows editing of the keypad’s system text. 

 

 

Battery replacement 

The  system  checks  the  battery  status  and  if  discharged  it  will  inform the 

end  user  or  the  installer.  The  keypad  will  continue  to  work  but  will  also 
indicate  a low  battery.  Batteries  should be  replaced  within 2  weeks  by  a 
qualified technician in service mode. 

Note: It is strongly recommended to change both batteries together 

and with identical types (manufacturer). 

Do not put expired batteries in the garbage, but follow local regulations.. 

 

O A S I S  8 0

A      

B      

C

A B C

?

B

A

IN

G N D
+ U

Отзывы: