olympia electronics GR-750 Series Скачать руководство пользователя страница 13

 

GR-750x series 

Control panel for addressable 
emergency luminaires 

Document number: 

923750400_90_001_EN 

Date: 25/5/2023 

Page: 13 of 15 

 

[13] 

 

Luminaire comm.

 

POINT 

1. Luminaire has no power.  
2. Luminaire has been removed.  
3. EMI (electromagnetic 
interference) on the 
communication line 
(Noise/Shortcircuit). 

• Verify the operation of the 

luminaire. Inspect for internal 
faults and faulty loop wiring.  

• Remove the luminaire from its 

base and reconnect it after 5 
seconds.  

• Check for nearby sources of 

EMI. 

Battery capacity

 

POINT 

The battery of the luminaire 
cannot hold sufficient charge. 

• Replace the luminaire’s battery 

with one of the same type and 
rating. (Refer to its user manual.) 

Battery

 

POINT 

1. Disconnected or missing 
luminaire battery.  

2. Luminaire’s battery is faulty.

 

• 

Check the battery connection.  

• Replace the battery of the 

luminaire. 

Charger

 

POINT 

Faulty luminaire charger circuit. 

• Replace the luminaire.

 

Lamp

 

POINT 

Faulty luminaire lamp. 

• Check the lamp of the 

luminaire and replace if needed. 

Wrong model

 

POINT 

1. Luminaire model has not been 
correctly detected/registered.  
2. Luminaire has been changed 
with a different luminaire model. 

• Manually configure the specific 

luminaire to the correct model 
(CONFIGURE POINTS menu). 

Printer board 

comm.

 

PRINTER 

1. Thermal printer card 
missing/not connected.  
2. Faulty thermal printer card. 

• Check the panel’s connection 

with thethermal printer card and 
replace if problem persists. 

Printer queue

 

PRINTER 

The printer’s buffer is full.

 

• Check if 

there is a problem that 

doesn’t allow the printer to print 

(no paper i.e.). 

Printer busy

 

PRINTER 

The printer’s buffer is full.

 

• Check if there is a problem that 
doesn’t allow the printer to print 

(no paper i.e.). 

Over 

temperature

 

PRINTER 

There is a problem with the 

printer’s head.

 

• Disconnect the printer from 

the panel, let it cool off and try 
again.  

• If the fault persists, replace the 

printer. 

Printer paper

 

PRINTER 

1. Thermal printer run out of 
paper.  
2. Problem with the thermal 

printer’s paper roll.

 

• Check the thermal printer for a 

paper jam.  

• Replace the paper roll with a 

new one. 

Comm. conflict

 

LOOP 

POINT 

Detected points with the same 
address on the same loop. 

• Verify that the address of each 

point connected to this loop is 
unique.  

• If duplicate addresses are 

found, assign another to one of 
them and register the point with 
the new address. 

Communication 

error

 

INTERNET CARD 

LOOP 

NIC 

PMU 

POINT 

The specific component/point 
has compatibility issues with the 
panel. 

• Contact the manufacturer.

 

Содержание GR-750 Series

Страница 1: ...GR 750x series Control panels for addressable emergency luminaires Quick installation guide...

Страница 2: ...3 1 3 Terms and definitions 4 1 3 1 Point 4 1 3 2 Emergency mode In emergency 4 1 3 3 Inhibit mode 4 1 3 4 Loop circuits 4 1 3 5 Function test 4 1 3 6 Duration test 4 2 INSTALLATION 5 2 1 Mounting th...

Страница 3: ...l network The maximum number of connected panels cannot exceed 24 The GR 750x series provides an ideal solution for medium to large scale facilities such as department stores hotels factories 1 2 Safe...

Страница 4: ...dresses and a maximum of 250 points connected to it 1 3 5 Function test Function test procedure initiates a self test operational test procedure of the luminaires connected to the panel to verify thei...

Страница 5: ...eries are connected Prior to any operation inside the enclosure of the panel ESD prevention measures should be taken The panel mounting area must be clean dry and free of collisions and vibrations The...

Страница 6: ...l panel has space suitable for two 12V lead acid batteries Pb with nominal capacity of 7Ah 9Ah 12Ah or 15Ah Both batteries must be the same model type and have the same nominal capacity The two batter...

Страница 7: ...on should be between 0 7mm2 and 2 5mm2 12 Low capacitance less than 200 pF m the total capacitance of a single cable should not exceed 400 nF Addressable Luminaire Connections 1 The GR 7500 can suppor...

Страница 8: ...e Figure 5 Closed loop topology Table 1 Recommended cable cross section Loop cable length 200m 500m 1000m 1500m 2000m Point Number 50 0 75 mm2 1 mm2 1 mm2 1 5 mm2 2 5 mm2 100 1 mm2 1 mm2 1 5 mm2 1 5 m...

Страница 9: ...se the address must be set using the panel by connecting and setting the luminaires one by one from the CHANGE POINT ADDRESS menu For more information on the point s address configuration refer to the...

Страница 10: ...opology repeat the previous step for loop cable each L and its corresponding LF line and each shield line start finish 7 If points are not connected using a loop topology no return line connect tempor...

Страница 11: ...ries in series and to the panel 7 Configure the date and time of the panel MAIN Technician Setting Time and date 8 Detect and register all connected points MAIN Technician Setup Find all points 9 Comp...

Страница 12: ...board FAULT NIC Faulty NIC board Replace with another NIC board Datetime not set PANEL Date and time have not been set to the panel Set the date and time DATE TIME MENU Non group member PANEL NETWORK...

Страница 13: ...Manually configure the specific luminaire to the correct model CONFIGURE POINTS menu Printer board comm PRINTER 1 Thermal printer card missing not connected 2 Faulty thermal printer card Check the pan...

Страница 14: ...nent s wiring connections Power supply PRINTER PMU There is a problem with the power supply Check the power supply Check the cable connections If the problem persists replace the component Short circu...

Страница 15: ...h the WEEE directive Electrical and electronic equipment should not be mixed with general waste Declaration of Conformity Olympia Electronics N Lakasas P Arvanitidis S A hereby declares that this prod...