GR-750x series 

Control panel for addressable 
emergency luminaires 

Document number: 

923750400_90_001_EN 

Date: 25/5/2023 

Page: 12 of 15 

 

[12] 

 

3.2  Troubleshooting 

FAULT

 

SOURCE

 

CAUSE

 

ACTION

 

Disconnected

 

BATTERY 

The batteries of the panel are not 
connected or faulty. 

• Check the batteries 

connections. 

• Replace batteries if problem 

persists. 

Overcharge

 

BATTERY 

Faulty PMU (battery charger) 
board. 

• Replace the PMU board.

 

Undercharge

 

BATTERY 

Faulty PMU (battery charger) 
board. 

• Replace the PMU board.

 

Ethernet/Wi-Fi 

comm.

 

INTERNET CARD

 

1. Network card missing/not 
connected.  
2. Faulty network card. 

• Check network card 

connection and replace if 
problem persists. 

Loop voltage 

(high)

 

LOOP 

Faulty loop board or short circuit 

on the loop’s cables.

 

 Replace with another loop 

board. 

Loop voltage 

(low)

 

LOOP 

Faulty loop board. 

• Replace with another loop 

board. 

FAULT 

NIC

 

Faulty NIC board. 

• Replace with another NIC 

board. 

Datetime not set

 

PANEL 

Date and time have not been set 
to the panel. 

• Set the date and time (DATE & 

TIME MENU). 

Non group 

member

 

PANEL NETWORK

 

There is a panel connected to the 
network, that is not part of the 

“trusted” panels group.

 

• Remove the panel or perform a 

new panel network group 
formation (GROUP FORMATION 
menu). 

PNet open ring

 

PANEL NETWORK

 

Disconnect between 2 or more 
panels of the panel network. 

• Check the panel network 

connections. 

PNet disconnect

 

PANEL NETWORK

 

No communication with a 
registered panel. 

• Check if the 

disconnected 

panel is still functional. 

• Check the network cable 

connections. 

• Check if the panel network 

settings have been altered. 

Earth fault

 

PMU 

1. USB cable connected.  
2. Short circuit between PE and 
loop cables.  
3. Panel not properly connected 
with PE line. 

• Check the mains power supply 

cable connections.  

• Check the loop cable 

connections. 

No mains supply

 

PMU 

No power supply from mains.  
 

•  Check the mains power supply 

cables/connections.  
 

 

 

 

 

Содержание GR-750 Series

Страница 1: ...GR 750x series Control panels for addressable emergency luminaires Quick installation guide...

Страница 2: ...3 1 3 Terms and definitions 4 1 3 1 Point 4 1 3 2 Emergency mode In emergency 4 1 3 3 Inhibit mode 4 1 3 4 Loop circuits 4 1 3 5 Function test 4 1 3 6 Duration test 4 2 INSTALLATION 5 2 1 Mounting th...

Страница 3: ...l network The maximum number of connected panels cannot exceed 24 The GR 750x series provides an ideal solution for medium to large scale facilities such as department stores hotels factories 1 2 Safe...

Страница 4: ...dresses and a maximum of 250 points connected to it 1 3 5 Function test Function test procedure initiates a self test operational test procedure of the luminaires connected to the panel to verify thei...

Страница 5: ...eries are connected Prior to any operation inside the enclosure of the panel ESD prevention measures should be taken The panel mounting area must be clean dry and free of collisions and vibrations The...

Страница 6: ...l panel has space suitable for two 12V lead acid batteries Pb with nominal capacity of 7Ah 9Ah 12Ah or 15Ah Both batteries must be the same model type and have the same nominal capacity The two batter...

Страница 7: ...on should be between 0 7mm2 and 2 5mm2 12 Low capacitance less than 200 pF m the total capacitance of a single cable should not exceed 400 nF Addressable Luminaire Connections 1 The GR 7500 can suppor...

Страница 8: ...e Figure 5 Closed loop topology Table 1 Recommended cable cross section Loop cable length 200m 500m 1000m 1500m 2000m Point Number 50 0 75 mm2 1 mm2 1 mm2 1 5 mm2 2 5 mm2 100 1 mm2 1 mm2 1 5 mm2 1 5 m...

Страница 9: ...se the address must be set using the panel by connecting and setting the luminaires one by one from the CHANGE POINT ADDRESS menu For more information on the point s address configuration refer to the...

Страница 10: ...opology repeat the previous step for loop cable each L and its corresponding LF line and each shield line start finish 7 If points are not connected using a loop topology no return line connect tempor...

Страница 11: ...ries in series and to the panel 7 Configure the date and time of the panel MAIN Technician Setting Time and date 8 Detect and register all connected points MAIN Technician Setup Find all points 9 Comp...

Страница 12: ...board FAULT NIC Faulty NIC board Replace with another NIC board Datetime not set PANEL Date and time have not been set to the panel Set the date and time DATE TIME MENU Non group member PANEL NETWORK...

Страница 13: ...Manually configure the specific luminaire to the correct model CONFIGURE POINTS menu Printer board comm PRINTER 1 Thermal printer card missing not connected 2 Faulty thermal printer card Check the pan...

Страница 14: ...nent s wiring connections Power supply PRINTER PMU There is a problem with the power supply Check the power supply Check the cable connections If the problem persists replace the component Short circu...

Страница 15: ...h the WEEE directive Electrical and electronic equipment should not be mixed with general waste Declaration of Conformity Olympia Electronics N Lakasas P Arvanitidis S A hereby declares that this prod...

Отзывы: