INSTALLATION INSTRUCTIONS

5

6

N
L

External 

switch

Controlled operation of the luminaire

Link

Permanent maintained operation 

L1

L

N

N
L

L1

L

N

1.

 Remove the front cover by unscrewing the retaining screws. Remove the acrylic plate.

2.

 

Always use in any case round mains cable, with a diameter of 12-14mm (H05RN-F type

    4x1mm² or any other type, at least equal to it’s mechanical and electrical properties).
    ATTENTION!! The cable must not be deformed in any way (This requirement is
    important to ensure the tightness isolation IP65). 

Pass the round cable through the cable

    gland and  tighten it all the way.

3. 

Unfasten the screw to remove the plastic cap (photo1) and connect the battery’s cable as

    shown in the photo 2. Replace the plastic cap and fasten the retaining screw.

4. 

Connect the mains cables as shown in figures 5 and 6. Yellow wire to GND,  blue to N, brown

    to L and black for maintained operation. The black wire can be connected to an external
    switch to control the maintained or non maintained operation of the luminaire. For permanent
    maintained operation use three wires to power the luminaire, GΝD for ground N for neutral, L
    for live wire and link the brown and black wire to the same terminal. 

5.

 Refit the acrylic plates and the front cover by srewing the removed screws in step 1.

6.

 Power on the device.

L1

L

N

4  

3  

The light source contained in this luminaire shall only be replaced by the manufacturer, or his 

agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.