Page
1 from
5
GENERAL
o
These devices are used indoors
(
ta 40 C
)
in
places where emergency luminaires are
needed. The luminaires
GR-290/WP and GR-
292/WP are suitable for corridors lighting and
the
GR-291/WP and GR-293/WP for open
a r e a l i g h t i n g
.
E a c h d e v i c e m u s t b e
permanently connected to mains power
supply
.
In normal operation the battery is
charging. In case of a mains power supply
failure the device will light the illumination
led automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions
ο
n page 2.
Battery Charging
The battery charging is completely controlled
.
In this case, is
achieved the perfect battery
maintenance
,
as well as the elongation of its
duration
.
When the battery has completely
charged
,
it charges with a maintenance
current.
Battery Cut-off
The device in this operation when the mains
power supply fails
and battery has lost its
energy
.
During this operation the device
enters the idle state
and battery consumption
is negligible, in order to be protected from
deep discharge.
Automatic Operational Test
It is conducted automatically every 15 days. In
order to be performed, the mains power
supply and the battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device’s back up operation
and emergency duration. The BATTERY
FAULT LED blinks during the measurement,
indicating this process to the user. This test is
conducted automatically every six months
.
In
order to be performed, the mains power
supply and the battery should be connected
and fully charged
.
If the battery is not fully
charged
,
the test is postponed
until the battery
is completely charged. If during this test, the
autonomy is less than the nominal then the
battery fault led turned on continuously and
the battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
WATERPROOF SELF TESTING NON MAINTAINED SPOT LIGHT
EMERGENCY LUMINAIRES WITH 1 WHITE POWER LED
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
CHARGE TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
220-240V AC / 50-60Hz
3 hours
1.5 hour
24 hours
Deep discharge and overcharge protection
IP65
4.8V/1.2Ah
270lm
160lm
1 white
power LED
o
5 to 40 C
Up to 95%
ABS/PC, PC
3 years
(1
year for the battery
)
430gr.
Ø125 x 65 mm
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Charge, lamp fault, battery fault
,
TEST button
GR-29
0
/WP
GR-291/WP
GR-292/WP
GR-293/WP
3.7W / 4.1 VA
TECHNICAL CHARACTERISTICS
(for LED MODULE specifications see page 4)
Thank you for your trust in our products
Olympia Electronics - European manufacturer
923293005_09_004