Page
1
from
6
923293003_09_006
GENERAL
o
This device is used indoors
(
ta 40 C
)
in
places where emergency luminaires are
needed. Each device must be permanently
connected to mains power supply
.
In normal
operation the battery is charging. In case of
a mains power supply failure, the device
enters emergency mode and the illumination
LED turns on. When the mains power
supply is restored the device turns to normal
operation.
Battery Charging
Battery Cut-off
To install the luminaire follow the installation
instructions
ο
n page 3.
INSTALLATION
The
battery
charging
is
completely
controlled
.
In this case, is
achieved the
perfect battery maintenance
,
as well as the
elongation of its duration
.
When the battery
has completely charged
,
it charges with a
maintenance current.
The device in this operation when the mains
power supply fails
and battery has lost its
energy
.
During this operation the device
enters the idle state
and battery consumption
is negligible, in order to be protected from
deep discharge.
This test can be done by pushing the test
button. The light source and the emergency
circuit of the device is monitored. The manual
test can be conducted only if the main power
supply and the battery is connected. During
this test period all indication LEDs are OFF.
Automatic Autonomous Test
Manual
Test
Automatic Operational Test
The Automatic Autonomous Test is conducted
and measures the device’s back up operation
and emergency duration. The BATTERY
FAULT LED blinks during the measurement,
indicating this process to the user. This test is
conducted automatically every six months
.
In
order to be performed, the mains power
supply and the battery should be connected
and fully charged
.
If the battery is not fully
charged
,
the test is postponed
until the
battery is completely charged. If during this
test, the autonomy is less than the nominal
then the battery fault led turned on
continuously and the battery must be
replaced.
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
SELF TESTING N
ON
-M
AINTAINED
EMERGENCY CEILING MOUNTED
LUMINAIRE
S
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (NiMh)
CHARGE TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
220-240V AC / 50-60Hz
1
.5
hour
24 hours
Deep discharge and overcharge protection
IP40
4.8V/1.2Ah
300lm
1 white
power LED
o
5 to 40 C
Up to 95%
ABS/PC
3 years
(1
year for the battery
)
439gr.
Ø125 x 63 mm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Charge, lamp fault, battery fault
,
TEST button
4.3W / 4.7 VA
TECHNICAL CHARACTERISTICS
(for LED MODULE specifications see page 5)
Olympia Electronics - European manufacturer
Thank you for your trust in our products
3 hours
150lm
GR-29
0
/M
GR-291/M
GR-292/M
GR-293/M