olympia electronics GR-1938/4P Скачать руководство пользователя страница 3

Page

 

3 from

 

4

1

  Unclip the plastic latches with a flat blade screwdriver, unfasten the 2 screws (not all the 

    

way, 

step 10 B

) and remove the diffusor. Place a flat blade screwdriver to the

 

recesses

    and pull up gently the reflector.  

2

  

Install the base plastic (with the included mounting screws and plugs). 

WARNING

!! 

To

    preserve the 

ΙΡ

65

 

rating, fit the screws with the metallic washers and plastic

 

rings

    which are included. 

3

  

Always use in any case round mains cable

,

 with external diameter

 

of 5

-

10mm

    (H05RN-F type 2x1mm² 

or 

any 

other type

,

 

at least 

equal 

to it’s mechanical and

    electrical properties).   
    ATTENTION!! The cable must not be deformed in any way (This requirement is
    important to ensure the 

ΙΡ

65

 

rating). 

Install

 

the gasket and make a hole in the center by 

    using a small screwdriver. Pass the round cable through the gasket. Install the second 
    included gasket in to the unused hole.

4

  Place the battery’s connector to the corresponding connector on the P.C.B

.  

 

Connect the mains cables to the respective terminal block

.  

6

  

Ν

 

for neutral

L

 for live wire

 

and 

L1

 for the maintained operation

The 

L

1

 

wire can be

    connected

 

to an external switch to control the maintained or non maintained operation of

    the luminaire

7

  

For permanent maintained operation use two wires to power the luminaire, 

Ν

 

for neutral

    and 

L

 for live wire, and link the 

L

 and

 

L1

.

8

  

Install the

 

included tie to fasten securely the power cables.

9

  

Refit the reflector (mind the holes of the indications).

10  

Finally place the diffusor (mind the holes of the indications). 

Attention!!

 

First the plastic 

      latches (A) must be secured 

(click sound)

 and then fasten the 2 screws (B) 

      (tightening torque 1.2 Nm)

.  

  

INSTALLATION INSTRUCTIONS FOR WALL OR CEILING MOUNTING

8

5

4

Charge

Lamp fault

Battery fault

Indications

7

N
L

Link

Permanent maintained operation

6

N
L

External

Switch

Controlled operation of the lamp

10

A

A

B

B

923193903_09_003

9

1

2

3