olympia electronics BSR-8020/WP Скачать руководство пользователя страница 8

Page

 

8 from

 9

Loop

Loop

4.7k

Ω

+

R

BS-572

-R

O

U

-

-

N

L

I

 +

UT

R

O

 +

L

IN

 

-R

O

U

-

-

N

L

I

 +

UT

R

O

 +

L

IN

 

-R

O

U

-

-

N

L

I

 +

UT

R

O

 +

L

IN

 

-R

O

U

-

-

N

L

I

 +

UT

R

O

 +

L

IN

 

-R

O

U

-

-

N

L

I

 +

UT

R

O

 +

L

IN

 

Conventional detector driving unit with external power supply

External

power

24V

Operation

Dip-switch setting

1

ON

2 3 4 5 6 7 8 9 10

1

ON

2 3 4 5 6 7 8 9 10

During an alarm, it

interrupts

the power to the zone to
reduce the consumption

 

During an alarm, the

power of the zone remains

in order to indicate which

detector issued the alarm.

+24V

 IN

NO

+IN

C

-IN

NC

ON

OFF

+L

+L

+L

-L

PE

PE

+L

+L

+L

-L

Connecting a BSR-8020/WP to conventional detectors

A 4.7k

Ω

 resistor must be installed 

on  the  last  detector

The  maximum  number  of  detectors  per  device  is 

40  conventional 

detectors  of  olympia  electronics.  According  to  EN  54  the  maximum  number  of 
detectors  per  zone  is  32  devices.  The  maximum  consumption  of  the  detectors 

in 

idle 

st

ate,

 must not exceed 

the 2.5

mA.

 

Additionally, the external power supply must be isolated from the main power grid and its 
power  must  be  calculated  depending  on  the  maximum  load.

 

If  for  example  we  have  10 

such  devices  and  each  device  consumes  30mA  during  an  alarm  then  the  power  supply 
must be capable of providing at least

 300

mA.

The  power  is  supplied  by  an  external  power  supply  and  thus  does  burden  the  loop.

 

The 

power  consumption  is  that  of  an  input/output  unit. The  external  power  supply  must  have 
an output range 

21-

28V

 

and must not be interrupted during a power failure.

 

921802002_09_005

Содержание BSR-8020/WP

Страница 1: ...lity to send to the panel with a suitable connection three states quiescent fault alarm 6 Reinstall the front cover and fasten the screws that were removed in step 1 The output unit contains a fully p...

Страница 2: ...which blinks periodically in the quiescent state is a power and good operation indication On the panel the input unit is shown as INPUT OUTPUT UNIT where is the set address of the device In this func...

Страница 3: ...On the 24V IN terminal you can connect an external power supply if the function conventional detector driving unit with external power supply is selected Indication LED Blinks periodically in quiescen...

Страница 4: ...3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4...

Страница 5: ...th an isolation lock When the lock is activated short circuit the output of the device does not operate and the message DISABLEMENT is shown on the panel The dip switch 8 of the BSR 8020 WP must be in...

Страница 6: ...wer supply from panel 56k 10k Loop Loop Operate as a Input unit Operation Dip switch setting Relay is activated for 5 seconds after a reset 1 ON 2 3 4 5 6 7 8 9 10 1 ON 2 3 4 5 6 7 8 9 10 The relay is...

Страница 7: ...24V IN NO IN C IN NC ON OFF L L L L PE PE L L L L Connecting a BSR 8020 WP with conventional detectors A 10k terminal resistor must be connected on the last detector The maximum number of detectors p...

Страница 8: ...stalled on the last detector The maximum number of detectors per device is 40 conventional detectors of olympia electronics According to EN 54 the maximum number of detectors per zone is 32 devices Th...

Страница 9: ...be returned to the premises of our company for repair or replacement as long as the warranty period is valid 72nd km O N R Thessaloniki Katerini WARRANTY HEAD OFFICE www olympia electronics com Olympi...

Отзывы: