![olympia electronics BSR-2104/MAR Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/olympia-electronics/bsr-2104-mar/bsr-2104-mar_operation-and-installation-manual_3869728057.webp)
Date
9/7/2018
File
BSR-2114/MAR
Document Number
921211401_09_002
Page
57 από 74
57
5.3.1
Check - points menu
!! BE AWARE !! THIS OPTION IS NOT ACCORDING TO EN 54-2.
This selection permits us to test each point that is installed on the loop.
The figure below shows a typical screen for testing one point of the panel. (figure 5-4).
Figure 5-4
Point Testing
The address of the point is referenced in the first 3 lines and can be changed using the keys
«LEFT»
or
«RIGHT»
or by pressing
the
«ENTER»
key.
The next 2 lines show the type and name of the installed point. If the point is not installed there is a “----“ beside the type.
In the next lines the panel refers to what it is reading from the loop and is the following:
TYPE
: The type of point on the loop.
VALUE
: The value that the point is reporting.
FLAGS
: meaningful only for the manufacturer.
CORRECT PACKETS RECEIVED
: Total amount of time that the panel communicated with the point successfully.
ERROR PACKETS RECEIVED
: How many times the panel receive data from the point with a wrong checksum.
CONFLICT PACKETS RECEIVED
: How many times the panel received data from the point with an incorrect format.
NO ANSWER PACKETS RECEIVED
: How many times the loop sends data and does not receive an answer.
TOTAL BAD PACKETS RECEIVED
: The total packets that come from the sum of the upper three categories.
5.3.2
Check Zones
With the option we can set or reset a zone to test mode. This menu has the below options:
ZONE
: Set or reset the test mode state of each zone.
ALL ZONES
: Set all zones to the mode.