background image

Page

 2

 from

 

5

the line(see figure 2). 

Connection with others fire panel.

Terminals  NO, C  are used to connect to the zone 
of the gas panel, as shown in figure 2. A terminal 
resistor should be installed on the end of the line 
(see figure 3). 

Programming Alarm latch mode

When  the  device  is  in  alarm  mode,  it  keeps  its 
condition even if the contents drop below  5-15% 

of the L.E.L. This is an alarm latch mode. This 
mode is helpful to the technician, to locate the 
device which is in alarm condition. 
When you connect the device to a conventional 
gas  panel,  the  device  must  have  alarm  latch 
mode. If we want to de-activate the alarm latch 
mode, the LD1 jumper must be linked. The link 
or the removal should be done when the unit is 
not  operating.  The  device  is  shipped  with   
activated the alarm latch. 

Figure 1. Diagram of removing the plastic cover

Ζ

1

2

4

V

_

M

5

Ê

6

Terminal Resistor

LED Alarm

Jumper for programming 
alarm latch mode

Fire panel 

Olympia Electronics

Relay resistance
selection jumper

Figure 2. Connection diagram of a detector 

with a fire panel of Olympia Electronics

921686000_09_01

7

These screws must be 
unscrewed in order to remove 
the plastic cover

The sensor must 
faced downwards

LED Alarm

Gland for cable 
connection 

Отзывы: