background image

  Using Actuators.

You can connect actuators in series. If you use 1 or 2 actuators you must  connect a resistor 2.7Ohm / 5W in series as 
shown below   on the right. If you use 3 or 4 actuators you just connected them in series. The maximum number of 
actuators are 4.

Π

Π

Π

Π

Π

2,7

Ω/5

W

Π

Π

Π

Π

Π

Π

The panel also has the following outputs:

24VM:

 A 24Vdc output that is interrupted in the event of a panel reset. It is mainly used for powering  gas 

detectors or other devices that need an interrupted power supply when the panel is resetting. If this output 
is short-circuited then the LED marked  'General fault' is lighted.

24VP:

  A    24Vdc  power  output  that  is  not  interrupted  in  the  event  of  a  reset.  It  can  be  used  to  power 

electromagnetic door latches

ZONE IN (ZP):

 

This output  can be used to communicate with a conventional panel 

B

S-632, BS-634 or BS-

Siren - Sounder Connections

Each panel offers 2 independent circuits for connecting sirens, bells or other devices that need 24Vdc in order 
to operate. Each circuit can supply to the devices a maximum of 300mA. Each terminal block by default has a 
pre-installed terminal resistor (5Κ6). This terminal resistor must removed and installed on the last siren of the 
line or is left on the terminal block if the circuit is not used.
The connections of both circuits are identical.

Figure 3

. Connecting 2  BS-531 sirens to the S1 output. This connection requires polarity.

5Κ6

5

Κ

6

Terminal

Resistor

Terminal

Resistor

Figure 4. 

Power supply connections for external devices.

Supplying the device with 

24

V DC

Permanent output

24

V DC

 

Interrupted output 

24

V DC

It is interrupted in case of 
a panel reset

Siren

S 1

S 2

Operation

Pre-alarm

Alarm-extinguish

Delay 

Without

Without

Zones activation

From any zone

From crossed zone 
or zone ZM

3-4 actuators typical connection 

1-2 actuators typical connection 

Figure 2

. Typical Connection

BS-531

Siren with

Beacon

BS-531

Siren with

Beacon

Page 6 from 

12

921627000_09_0

10

Содержание BS-627

Страница 1: ... two independent siren outputs One contact relay for fault status Two fully programable relay contacts Terminals to communicate with conventional fire detection panels The batteryΑ 986 12V 7Ah is required for the operation of the panel All functions and indications are according to European Norms ΕΝ 12094 1 EN 54 2 EN 54 4 Press for immediate extinguishing Insert the key to access the internal of ...

Страница 2: ...have an ALARM condition The Fault LED lights in every FAULTcondition The Disable LED lights in every DISABLE condition The System LED lights when occurred a problem in the central possessor unit System fault The next indication LED groups are the ZONE and ALARM These indicators light when the corresponding issues an alarm condition Below this group we have the Fault Disable indication for each zon...

Страница 3: ...e picture the extinguish output is deactivated To restore the button to its previous position turn it anti clockwise Access level 2 Includes all the functions that the user can do and an access code is required The code is 34 it is the same for all panels and cannot be changed The functions that can be implemented using this code are the following Siren Silence When an alarm is issued and we want ...

Страница 4: ...and Relay 2 then we must enter the technical code 364 and then press the number key 5 The General fault and General alarm LEDs start to blink The Fault Disable LED of zone 1 and zone 2 show the programmed activation method of the zone relays according to the table below We can see the programming process of the Relay 1 and Relay 2 operation in zone 1 and 2 Alarm LEDs according to the table below Β...

Страница 5: ... O N L I R O U T L N I T U R O N L I R O U T L N I T U R O N L I R O U T L N I T U R O N L I To the BS 63X zone Το Relay1 terminal of a BSR 2104 or BSR 2114 R1 alarm relay 1 R2 alarm relay 2 RF fault relay Figure 1 Connecting devices to BS 627 panel Page 5 from 12 BS 527 BS 527 921627000_09_010 OUT IN 470Ω 0 5W BS 537 BS 533 No1 ...

Страница 6: ...h panel offers 2 independent circuits for connecting sirens bells or other devices that need 24Vdc in order to operate Each circuit can supply to the devices a maximum of 300mA Each terminal block by default has a pre installed terminal resistor 5Κ6 This terminal resistor must removed and installed on the last siren of the line or is left on the terminal block if the circuit is not used The connec...

Страница 7: ...agnetic door latch activation electro valves activation Output FR This output is used to be connected with the output Fire Routing of the BSR 2104 and BSR 2114 as shown in figure 1 OUTPUT A A This output is used only for production proposes This must not be used by any other technician but only technician from olympia electronics CONNECTION OPTIONS IN ADDRESSABLE OR CONVENTIONAL PANEL For connecti...

Страница 8: ...sconneted from the mains power supply and the battery The installation of the panel must be carried out by qualified personnel only Disconnect power before servicing Never insert or remove boards or componets with the power on During installation use grounded antistatic wrist band to protect this equiment form ESD The panel must be installed permanetly It is not allowed to connect the device direc...

Страница 9: ...atic circuit breaker rated at 10A This fuse has to be a separate labeled fuse 4 Always use cables with double insulation 5 The diameter of the cable must be at least 1mm Figure 9 6 The inner insulation of each cable must not be cut more than 1cm Figure 9 7 The outer insulation must not be cut more than 1cm away from the internal insulation 8 The batery fuse is a resetable fuse 3A inside the panel ...

Страница 10: ...brake glass call points maximum current 10mA 26VDC 3VDC reset interrupted output with maximum current output 0 3 A The output is protected with a self reseting electronic fuse Output 24VM The relay 1 and 2 contacts have value of 5Α 250VAC The fault relay contacts have value 1Α 30VDC Under no circumstances should voltages or currents outside limits be connected All relays output must be protected w...

Страница 11: ...raph 7 8 EN 54 2 Design Activation time of manual trigger Activation time of outputs after trigger Components of the panel have been selected for the intended purpose and are expected to opetate within their specification when the environmental conditions outside the cabinet of the panel comply with class 3k5 of EN 60721 3 3 1995 Class A temperature range of 5 C to 40 C A factory production contro...

Страница 12: ...Page 12 from 12 921627000_09_010 Certification The panel BS 627 is certrified from HEEQAC Also HEEQAC controls the production under CPR number 0848 CPR 005 Below is the marking ...

Отзывы: