Once the device is connected to the panel's network, remove the battery and wait for 10 seconds. 
Then press the 

tamper

 and re

install

 the battery. Wait until the 

LED 

lights up. Once you release the 

t

amper, the 

LED

 will go out. In this case, the range

 test

 will start.

 

During 

range test

 the device LED 

blink

s every second. The duration of 

range test

 is 60-95 seconds. When it is finished the LED 

goes off 

and after 2 seconds the

 test

 result 

is displayed

 as follows:

Single

 

blink

:

 

Strong signal.

 The device can be 

safely installed 

at this point.

Two 

blink

s:

 

Normal signal.

 The device can be safely 

installed

 at this point.

Three 

blink

s:

 

W

eak signal.

 It is 

recommended

 not to 

install

 the device 

at this point. T

he

re will be

                                              communication bettween the device and the control panel 

but there will

                                              

be communication packet

s losses

.

Four 

blink

s:

 

Out of range.

 The 

device

 is forbidden to be placed in th

is point

.

Note

: As  soon  as  the 

test

  procedure  is  started,  it  is  suggested  that  the 

device 

c

over

 

will 

be  placed 

directly  in  order  to  simulate  the  actual  communication  conditions.  The  environment  must  be  also

 

adapted to the worst possible conditions (eg closed doors). 
Finally, in case of 

home improvements or renovation

, it is suggested 

to perform a

 

range test 

again

.

RANGE TEST 

RANGE TEST 

BATERRY REPLACEMENT

BATERRY REPLACEMENT

The detector checks its battery voltage and transmits the information to the panel. 

When

 the 

control 

panel  displays  a  low  battery  indicator,  the  detector 

will 

continue  to 

operate

  for  at  least  2  weeks.

 

N

evertheless 

it is 

recommended to replace the battery as soon as possible. This must be done by a 

qualified technician

 and

 the control panel

 must be 

in 

s

ervice mode

.

I s not allowed to discard batteries in to common trash bins, they must be discarded only 

t i

 

in battery recycling points. Do not incinerate.

Page 4 of 5

9214

70000

_09_005

 KL1

Figure 1

Example of con

nection 

NC

 external

 magnetic contacts

with BS-470

The device can be connected to external magnetic contacts via the 

KL1

 terminal

 block

 (Figure 

1

). If a magnetic field 

is connected to this input, the device sends an alarm signal to the 

control 

panel.

 If

 the contact is not connected to an 

external device, at the 

cable 

terminal

 

of the 

KL1

, the

n

 manufacturer

’s cable

 must remain.

N

OTE:

The maximum distance of the external sensor cable is 3 meters !!!

CONNECTION WITH EXTERNAL MAGNETIC

 CONTACTS

CONNECTION WITH EXTERNAL MAGNETIC CONTACTS

Содержание BS-470

Страница 1: ...ither on a flat surface or at an angle of surfaces when required The device must be mounted in such a position in order to permit the best possible surveillance The mounting height should be between 2 2 and 2 5 meters with an ideal height of 2 4 metres In order to avoid unintended false alarms the detectors must not be mounted in areas that have hot air or air drafts in general such as over radiat...

Страница 2: ...ted to gently remove the circuit board by removing its retaining screw as shown in the photo 3 of page 3 Take care not to touch the IR sensor surface This will affect is operation Photograph 4 page 3 shows the interior of the plastic base as well as the cable entry and mounting hole positions To mount the unit to the wall increase the hole diameter of points Α to 4 mm using a suitable drill bit an...

Страница 3: ...from the control panel zone with delay or zone without delay Attention Selecting the delay zone from the board is required by BS 468 A DIP switch 2 When is set to OFF the device is in normal mode When is set to ON it is in high sensitivity mode and increases the detection range It also has a terminal for connecting an external magnetic contact which when not in use must be short circuited Wall mou...

Страница 4: ... the worst possible conditions eg closed doors Finally in case of home improvements or renovation it is suggested to perform a range test again RANGE TEST RANGE TEST BATERRY REPLACEMENT BATERRY REPLACEMENT The detector checks its battery voltage and transmits the information to the panel When the control panel displays a low battery indicator the detector will continue to operate for at least 2 we...

Страница 5: ...ight to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection Olympia Electronics reserves the right to charge or not the buyer the transportation cost HEAD OFFICE 72nd km O N R Thessaloniki Katerini P C 60300 P O Box 06 Εginio Pierias Greece www olympia electronics gr info olympia electronics gr POWER SUPPLY BATTERY LIFE COMMUNICATION RANGE DE...

Отзывы: