Alarm relay

The  alarm  relay

 

is  activated  when  the 

concentration

  % 

L

.

E

.

L

of  the  sensed  area 

exceeds  the  alarm  level 

(10% 

or

  20%)

The

 

relay

 

returns

 

to  normal  operation  when  the 

gas concentration returns to normal levels

If  the 

latch  function  has  been  selected 

via 

the

 

S

3

  switch

then 

 

the  relay  remains 

activated  even  if  the  gas  levels  return  to 
normal

.

 When 

we 

connect the device to a fire 

detection  panel,  the  device  needs  to  have  an 
alarm  lock.  This 

happens

  that  the  user  can 

understand which device has given an alarm.

Fault Relay

The  fault  relay  has  one  contact  that  is  closed

 

(

N

.

C

.) 

when  the  system  is  powered  and  there 

are no malfunctions

This contact opens when 

there is no power or there is a malfunction

.

Green LED

 (

operation indicator

)

The  green  LED  indicates  the  presence  of  the 
power  supply  and  special  operation  states  as 
described in table 2.

Red

 

LED

 (

alarm indicator

)

The  red  LED  is  activated  when  the  gas 
concentration of

 % 

L

.

E

.

L

in the covered area 

exceeds  the  selected  alarm  level

  (10% 

or

 

20%). 

The LED

 

is 

deactivated when the gas 

concentration  returns  to  normal  levels

.

 

If 

the 

latching  function

  has  been  selected  via 

the  S3  micro  switch  then  the  LED  remains 
active (

blinks every second

even if the gas 

concentration drops to a safe level.

 

Yellow

 

LED

 (

Fault indicator

)

T h e   y e l l o w   L E D

 

i n d i c a t e s   a   s y s t e m  

malfunction  or  fault  and  also  some  special 
states as shown in table 3.

System Calibration
WARNING

!!!

 

The  calibration  procedure  of  the 

detector  must  be  done  by  qualified  personnel 
that have previously read the user manual.

-

The  special  calibration  function  is  not 

available  to  the  user  if  there  are  faults  in  the 
system.
-For  the  calibration  procedure  using  a 
reference  gas,  the  OL-11  calibration  kit  is 
required.

 (

figure

 

6

). 

-For  the  calibration  procedure  using  a 
reference  gas,  a  mixture

  20%  or  50%  L.E.L. 

with  oxygen  and  nitrogen  is  used

.  The 

explosive gas catalytic sensors do not operate 
without oxygen.

Page

 

5 from

 

7

Yellow LED Operation

Permanently activated

Problem with the system settings

Repeat the clear air and reference gas calibration
procedure.

 

Probable cause:
-The power supply of the system is out of operation limits

 

 

(

in combination with the green led operation

). 

 

Check the power supply of the system.

-gas sensor malfunction

.

 

Replace sensor.

 

-Central processor malfunction

Service required.

Explanation

TABLE 3

Intermittent brief

illumination once a minute

The current concentration of gas has exceeded the 
high detection limit of the device that is

 50% 

L

.

E

.

L

.

Normal operation is restored

 

automatically when

the gas concentration drops to within the measuring
limits of the unit.

 

Intermittent operation

every second

Green LED Operation

Permanently activated

Intermittent operation

every second

The system is powered

Explanation

TABLE 2

The system is in the initialize pre-heat phase 

of the sensor

This phase last for 60 seconds

Intermittent brief

illumination once a minute

The supply of the system is out of limits

92137

500

0_09_007

Содержание BS-375/WP/A

Страница 1: ...ars 60 seconds 45 seconds 1 5 L E L 1 5 L E L 4 5 L E L year Operation LED green Alarm LED red Fault LED yellow Selectable at 10 and 20 L E L 3VA IP65 EN 60079 29 1 50270 50271 o 10 to 60 C 1 atm 10 1...

Страница 2: ...n the jumper is inserted the resistance is zero and an external resistor can be used When the jumper is not placed there is an internal resistor of 440 The device operates with 10 30VDC 7 5 21VAC ATTE...

Страница 3: ...tton can be used S4 This operation refers to the special operation calibration function with reference gas Via S4 select the concentration of gas that will be used 20 or 50 L E L S5 This setting refer...

Страница 4: ...Figure 4 Connecting 4 gas detectors to an olympia electronics conventional panel Apart from connecting the zone terminal blocks the detectors must be powered using the 24V terminal blocks The total n...

Страница 5: ...le 3 System Calibration WARNING The calibration procedure of the detector must be done by qualified personnel that have previously read the user manual The special calibration function is not availabl...