These  switches  determine  the 

operation  of  special  maintenance  and  test 
functions.

 

To  conduct  these  functions,  select 

the  suitable  combination  with  the  switches

 

S

and

 

S

and  press  the  internal  button

 

BT

(

figure

 3) 

for more than 1 second

.

The function

 

«

output  test

» 

activates  all  the  LEDs  and  the 

alarm  relay  and  deactivates  the  fault  relay 
while  the  button  is  being  pressed

For  the 

calibration  function,  detailed  instructions  are 
given later on in this manual.

-

S

3.

 

When  the  latching  function  is  selected 

t h e n   w h e n   t h e   d e t e c t o r   s e n s e s   a   g a s  
concentration equal to or greater than 

L

.

E

.

L

 

the alarm relay and the alarm led (red) remain 
activated even if the concentration of 

 % 

L

.

E

.

L

returns to normal levels.

 

The deactivate them, 

an external button can be used.

 

-

S

4.

 

This  operation  refers  to  the  special 

operation  calibration  function  with  reference 
gas.  Via  S4  select  the  concentration  of  gas 
that will be used

 (20% 

or

 50% 

L

.

E

.

L

.)

S

5.

 

This  setting  refers  to  the  concentration  in 

 

L

.

E

.

L

that  must  be  detected  in  order  to 

activate  the  alarm  relay,

 

the  red  led  and  the 

zone  output.

  10% 

or

  20% 

L

.

E

.

L  can  be 

selected

After  the  selection  is  made,  the 

concentration  of  gas  that  is  considered  to  be 
normal is below

 2.5% 

L

.

E

.

L

from the selected 

setting

that  is  below 

  7.5% 

or

  17.5% 

L

.

E

.

L

respectively.

Figure

 

2

C

onnection 

with f

ire detection panel Olympia Electronics

Z

1

2

4

M

Fire detection panel

 Olympia Electronics

Terminal

resistor

8,2Κ

 

Figure

 1. 

Interior access, cable entry and indicators

To gain access to the interior remove
these 4 screws

Sensor head located downwards

Cable entry groumet

Operation, Alarm and Fault
Indicator

Capability to install a second
cable groumet.

Page

 

3 from

 

7

92137

500

0_09_007

Содержание BS-375/WP/A

Страница 1: ...ars 60 seconds 45 seconds 1 5 L E L 1 5 L E L 4 5 L E L year Operation LED green Alarm LED red Fault LED yellow Selectable at 10 and 20 L E L 3VA IP65 EN 60079 29 1 50270 50271 o 10 to 60 C 1 atm 10 1...

Страница 2: ...n the jumper is inserted the resistance is zero and an external resistor can be used When the jumper is not placed there is an internal resistor of 440 The device operates with 10 30VDC 7 5 21VAC ATTE...

Страница 3: ...tton can be used S4 This operation refers to the special operation calibration function with reference gas Via S4 select the concentration of gas that will be used 20 or 50 L E L S5 This setting refer...

Страница 4: ...Figure 4 Connecting 4 gas detectors to an olympia electronics conventional panel Apart from connecting the zone terminal blocks the detectors must be powered using the 24V terminal blocks The total n...

Страница 5: ...le 3 System Calibration WARNING The calibration procedure of the detector must be done by qualified personnel that have previously read the user manual The special calibration function is not availabl...

Страница 6: ...In its position install the accessory OL 11 1 of the calibration kit OL 11 figure 6 4 Install the part OL 11 2 on the part OL 11 1 figure 6 5 Select via the micro switch S4 figure 3 the concentration...

Страница 7: ...repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or...

Отзывы: