olympia electronics BS-304 Скачать руководство пользователя страница 4

 

Page 4 from 22  

 

921316000_09_016 

 

 

 

1.3 

Access level 1 

 

This level contains 2 functions that can be implemented by pressing a single key. 
 

-

 

In  the  event  of  an  Alarm  or  Fault  condition,  if  the  key  number  (1)  is  pressed  then  the  internal  buzzer  is 
silenced. For as long as the event is in effect the internal buzzer sounds once in every 30 seconds. Should 
the panel see a new event in this state then the buzzer will start to sound continuously.  

-

 

When  the  panel is  in  standby  mode  (no  alarm or fault  events  have occurred)  then  if  the key number (2) 
(lamp test)  is pressed the system conducts a sequential LED and Display test. 

 
When the system is in quiescence state, the lcd screen shows info about the system. 
The below screen shows some information about the system 
 
 
 
 
 
 
 
The below screen shows the panel name and the technician information. 
 
 
 
 
 
 
 
The next screen shows the condition of each sensor (input)

 

 
 
 
 
 
 

 

The sensors 4-20mA incorporates the current have the next situations:

 

 

 

FAULT -  

(<1 mA)

 

 

 

UNDERFLOW

 (from 1 to 3.5 mA)

 

 

 

NORMAL

  (from  3.5  to  21  mA)  inside  these  limits  we  can  do  the  setup  of  alarm  1,  alarm  2  and 

alarm 3)

 

 

 

OVERFLOW

 (from 21 to 24mA)

 

 

 

FAULT+

 (24mA and Higher). 

 

There is the disable situation (

ΝΟ CONFIGURATION

 
 

In case alarm or fault the LCD display shows the corresponding message.

 

 

 

This screen shows a summary of the events in the system. 
 

 

The alarm screen show which inputs are in alarm condition. 
For  example  the  second  line  4:  14%  LIE  ALARM  2  means  that  the  4th  input 
sensor has detected 14% LIE of a gas and it is at ALARM 2 state. 
 
 

 

The screen on the left shows the faults of the system. 
For example the second line 1: FAULT + means that the 1st input sensor  has a 
FAULT +. 
 
 

   EVENTS IN SYSTEM 
ALARMS           10 
FAULTS            5 

 

ALARM  

     10 

 4:  14%LIE ALARM 2  
 9:  60ppm  ALARM 3 

16:  20ppm  ALARM 1

 

FAULT  

      5 

 1:  FAULT +  
 3:  FAULT - 

BATTERY

 

OLYMPIA ELECTRONICS 
   BS-316   V.055 
 12:00:00  20/01/10 

 SYSTEM READY

 

  PANEL NAME 
MAIN BUILDING 
  TECHNICIAN INFO 

OLYMPIA ELECTRONICS

 

 1:   0%LIE NORMAL 
 2: NO CONFIGURATION  
 3: NO CONFIGURATION  

 4:   5ppm  NORMAL 

 

Содержание BS-304

Страница 1: ...Page 1 from 22 921316000_09_016 BS 304 BS 308 BS 312 BS 316 Gas detection control panel up to 16 inputs Installation operation manual...

Страница 2: ...th the mains power supply 230V AC and with the battery 7 2 5 2 Sensor connectivity 8 2 5 3 Output connectivity 10 2 5 4 Other outputs and their use 11 2 6 Network connection 11 3 Technician menu 12 3...

Страница 3: ...n about each event i e Alarm sensor 1 that means alarm from sensor 1 Under the display there are 6 buttons for controlling the panel On each button there is a number 1 6 and corresponds to the functio...

Страница 4: ...The sensors 4 20mA incorporates the current have the next situations FAULT 1 mA UNDERFLOW from 1 to 3 5 mA NORMAL from 3 5 to 21 mA inside these limits we can do the setup of alarm 1 alarm 2 and alar...

Страница 5: ...he battery was disconnected at 11 00 on 18 01 10 The screen on the left shows the panel start operating from 09 00 on 10 01 10 1 4 Access level 2 User access level All the functions of access level 2...

Страница 6: ...gas detector anti explosive type BS 393 Ammonia detector anti explosive type On the AUX input we can connect fire detection buttons like the BS 536 BS 7000 IP 65 We can program and work the panel by u...

Страница 7: ...t the new battery must be of the same type Two cables with connectors are used to connect the battery to the panel The black cable is connected to the negative pole of the battery marked with or with...

Страница 8: ...o and S of the panel as shown in figure 4 The cross section of the cable depends on the length see next table On all sensors with 2 contacts you must connect a coaxial cable The shielding of the cable...

Страница 9: ...Up to 500 meters 3 x 1 5 mm Up to 600 meters 3 x 2 5 mm The gas sensors need a preheat time in clear air for about 20 seconds After this time the sensor can sense gases but the maximum sense ability i...

Страница 10: ...ween inputs and S of Figure 6 Figure 7 Connection diagram for BS 531 Output connectivity On the panel there are 16 programmable outputs relay Each relay has a triple connector NO NC C For more informa...

Страница 11: ...AUX must not be more than 300mA Network connection It is possible to have network of panels In each network each panel has a unique address The central panel has address 1 and sub panels have address...

Страница 12: ...ode in entered the operator has access to level 3 functions TECHNICIAN MENU CONFIGURATION INFORMATION PARAMETERS ENABLEMENT DISABLEMENT CHECK SENSORS RELAY ZONES SENSOR RELAY ZONES BATTERY MAINS SUPPL...

Страница 13: ...n is shown where you can choose which sensor you want to setup SETUP SENSOR UNIT LOAD SETUP SENSOR NAME INCREASING ZERO RANGE ALARM2 ALARM3 RELAY ALARM2 RELAY ALARM3 RELAY FAULT ZONE SAVE SENSOR RELAY...

Страница 14: ...fault at the sensor ZONE the zone of the sensor At next table we can see some typical values Type Gas Zer o Limit Unit Alarm 1 Alarm 2 Alarm 3 BS 380 LPG 0 20 LIE 7 10 20 BS 381 Methane gas 0 20 LIE...

Страница 15: ...e relay works normally activated Positive Logic NC or normally deactivated Negative Logic NO LATCHED OUTPUT it indicates if you want to keep the output active even if the gas concentration returns und...

Страница 16: ...technician can be informed for all the system The below diagram shows the menu INFORMATION SENSORS ZONES BATTERY MAINS SUPPLY VCC VOLTAGE RELAY An example of the information of a sensor screen are Th...

Страница 17: ...on 3 or 4 An example of the information zone screen is the above screen shows the relay on alarm 1 relay on alarm 2 relay on alarm 3 and relay on fault respectively To change the relay use the button...

Страница 18: ...ed If the address is the panel is a master panel If the the address is from 2 to 16 the panel is a subpanel NETWORK DETECTION if the panel is a master panel address 1 we can make a network detection F...

Страница 19: ...ardware of the pane l CHECK SENSOR LAMP TEST RELAY Figure 15 Check Menu On Check sensors the below screen appears to see the other sensors press 3 or 4 The screen to check the relay is ENABLEMENT ENAB...

Страница 20: ...l is restored 6 Leave the panel working for about 20 minutes without cutting off the power supply Check the current of every sensor The current must not be over 4mA If it isn t wait about 1 hour and t...

Страница 21: ...rovided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our com...

Страница 22: ...keep them for future reference Title 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Sensor s Model ZERO RANGE UNIT Alarm 1 OUTPUT 1 Alarm 2 OUTPUT 2 Alarm 3 OUTPUT 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 DE...

Отзывы: