VENTILATION & COMBUSTION AIR

WARNING:

WARNING:

WARNING:

WARNING:

WARNING:

AIR OPENINGS TO COMBUSTION AREA MUST NOT BE

OBSTRUCTED.  BY FOLLOWING THE INSTRUCTIONS BELOW, ADEQUATE
COMBUSTION AIR CAN BE MAINTAINED

COMBUSTION AIR REQUIREMENTS

(Minimum Opening Requirements)

*

UNCONFINED AREA

**

CONFINED AREA

Outside

Inside

Outside Combustion Air

Combustion

Combustion

VERT. DUCTS

HORZ. DUCTS

BTU/HR

Air 1 IN.

2

Air 1 IN.

2

1 IN.

2

1 IN.

2

INPUT

/5000 BTU/HR

/1000 BTU/HR

/4000 BTU/HR

/2000 BTU/HR

(Paragraph 4)

(See Fig 1)

(See Fig 2 & 3

(See Fig 4

(MIN. 100 IN

2

)

Pages 5 & 6)

Page 6)

91,000

19

100

23

46

140,000

28

140

35

70

***** Unconfined area:

 A space whose volume  is not less than 50 cubic feet per

1000 BTU per hour of all appliances installed in that space (cubic feet of space = height x
width x length).

**

**

**

**

** Confined area:

 A space whose volume is less than 50 cubic feet per 1000 BTU

per hour of all appliances installed in that space (cubic feet of space = height x width x
length).

1. Ventilation of the boiler room must be adequate to provide sufficient air to properly

support combustion.

2. When a boiler is located in an unconfined space in a building or conventional construction

frame, masonry or metal building, infiltration normally is adequate to provide air for
combustion and ventilation. However, if the equipment is located in a building of unusually tight
construction the boiler area should be considered as a confined space. In this case air for
combustion and ventilation shall be provided according to part 5 on page 6.  If there is any
doubt, install air supply provisions in accordance with section 5.3, Air for Combustion and
Ventilation, of the latest revision of the NFPA 54 code.

3. When a boiler is installed in an unconfined space, in a building of unusually tight

construction, air for combustion and ventilation must be obtained from outdoors or from
spaces freely communicating with the outdoors. A permanent opening or openings having a
total free area of not less than 1 square inch per 5,000 BTU per hour of total input rating of
all appliances shall be provided. Ducts may be used to convey makeup air from the outdoors

Содержание OSW

Страница 1: ...ENTING ADDENDUM VENTING ADDENDUM VENTING ADDENDUM VENTING ADDENDUM VENTING ADDENDUM OSW OSW OSW OSW OSW OIL FIRED DIRECT EXHAUST CAST IRON BOILER Olsen Technology Inc P O Box 900 Wallaceburg Ont N8A5E...

Страница 2: ...fit the vent adapters to the pipe and check for fit before applying RTV silicone 6 Place a bead of RTV high temperature silicon on each vent adapter see fig 4 and screw the adapters counter clockwise...

Страница 3: ...eturn piping If not installed first installation of vent pipe will be difficult 2 Insert vent pipe in boiler vent outlet apply silicone completely around edge of outlet and tighten clamp See figure 5...

Страница 4: ...PAGE 3 FIGURE3...

Страница 5: ...PAGE 4 FIGURE4 FIGURE5 CA CA CA CA CAUTION UTION UTION UTION UTION KEEP AREA AROUND THE VENT TERMINAL FREE OF SNOW ICE AND DEBRIS...

Страница 6: ...Ventilation of the boiler room must be adequate to provide sufficient air to properly supportcombustion 2 Whenaboilerislocatedinanunconfinedspaceinabuildingorconventionalconstruction frame masonry or...

Страница 7: ...ree area of the area of the openings to which they connect The minimum dimension of rectangular air ducts shall be not less than 3 x 3 inches or 9 square inches A Wheninstallingtwoopenings onemustcomm...

Страница 8: ...ing of all equipment located in the enclosure The free area must be no less than the sum of the areas of all vent connectors in the confined space 6 In calculating free area using louvers grilles or s...

Отзывы: