Specification of
Liquid pipe
12.7
9.52
6.35
Max. length
20m
15m
25m
R22
(L-5)X0.05kg
(L-5)X0.03kg
(L-5)X0.10kg
The additional refrigerant should be charged from the service port of the 3-way valve
when the appliance is operating in cooling mode.
Do not allow air enter the refrigeration system while charging refrigerant.
(* "L" refers to length of connection pipe.)
Open/Close the valves
Open/Close the spools or the valves of outdoor unit with a
f
5mm hexagon spanner.
!
WARNING
Specified power cables should be used. Do not apply any pressure on the
terminals used to connect.
Grounding must be properly done.
Improper connection may cause fire.
Electric Wiring must be done by professionals. Use a separate circuit according
to national regulations.
The grounding wire should be away from gas pipes, water pipes, telephone,
lightening rods or other grounding wires. Improper grounding may cause electric
shock.
If the wiring capacity is not enough, electric shock or fire may occur.
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similarly qualified person in order to avoid a hazard
An all-pole disconnection switch having a contact separation of at least 3mm in all poles sho-
uld beconnected in fixed wiring.
Be sure to Install Current Leakage Protection Switch. Or electric shock may occur.
the appliance must be positioned so that the plug is accessible
the appliance shall be installed in accordance with national wiring regulations
CAUTION
ELECTRIC WIRING
16
R410A
The temperature of refrigerant circuit will be hight ,please keep the interconnection able
away from the copper tube.
(L-5)X0.054kg
(L-5)X0.022 kg
(L-5)X0.11kg