OLIVER
IGD
OLIVER
IGD
REMOTE PORT NOT
TEST RELAYS ON
SENSORS (J16)
CABLE C1 ONLY
The FIND ADD RELAYS Command
If addressable Tocsin 107 series I/O Nodes are cabled to either port 1 or 2 of the control panel then the
FIND ADD RELAYS command can be used to check that the Tocsin 700+ can communicate to them.
The function first checks if port C2 is set for SENSORS option, if not it is ignored. The function then
interrogates the highways and reports how many addressable relays have been discovered and what
addresses and cable numbers (C1 or C2) they are on.
1
2
3
4
Select the FIND ADD RELAYS menu item
and the following setup screen is displayed.
The function first checks the selection on port
C2. If the PORT setting is SENSORS then it
is checked, if not then it is ignored (as in this
example).
FOUND = 4
NO CHANGES MADE
1 of 4 = 4201 (C1)
The system now checks through each
possible address in the range 4200 to 4299
and tries to communicate to each address in
turn.
The top line of the display now indicates the
number of relay addresses found and the
bottom line indicates each address in turn
and its cable location as the jog wheel is
pressed
On the final press of the jog wheel the system
reports ‘NO CHANGES MADE’ as this is an
information only option.
The display then advises set up of the relays
on AL1,2 or 3 manually as no auto set up is
possible.
Note that 8 way relay extender boards can
also be discovered using this option.
Page 38 of 52