Oliver IGD TOCSIN 102 SERIES Скачать руководство пользователя страница 4

OLIVER

IGD

16.0

ACCESSORY THREAD

170.0

130.0

65.0

23.0

77.5

40.0

155.0

Ø25.5

Ø20.0

2 OFF Ø20.0

23.0

23.0

NOM 76

Ø25.5

KNOCK OUT

KNOCK OUT

KNOCK OUT
OPPOSITE
FACES

Ø5.5

Ø25.5 (BLANKED)

190.0

Non ATEX versions with MK6 detectors, Mounting Details

The non-ATEX version, 103 series flammable gas detector is typically fitted in areas that do not 

require a flameproof gas detector approval. Typical applications would be boiler rooms, school 

laboratories, commercial kitchens etc. Cabling should have a suitable level of protection for the 

area into which the detector is fitted and be of a screened type such as CY style cable or FP200 

style cable. Cable glands should provide a positive seal to limit ingress from dust and moisture.

Page 4 of 9

172
158

44

Physical Size TOC-31A Version

Physical Size TOCSIN 103 Version

Physical Size TOC-31A Version

3 OFF M20 ENTRY HOLES

148.0

88.0

13.0

47.0

18.0

97.6

5.0

5.0

MK6 Detector

76

98

18

20mm Entries Top, Bottom 
& Either Side 

M22 x 1.5

Содержание TOCSIN 102 SERIES

Страница 1: ...ationalgasdetectors com www internationalgasdetectors com IGD OLIVER Triton House Crosby St SK2 6TS England Oliver IGD Limited Ref T102P VERSION 6 00 TOCSIN 102 103 TOC 30 SERIES PELLISTOR OPERATION M...

Страница 2: ...of how well the system is installed and calibrated Oliver IGD Limited can help advise on the correct siting and calibration of gas detectors Mounting And Cable Information 145 0 126 0 128 5 COVER SEC...

Страница 3: ...glands and blanking plugs should have O Ring seals or sealing washers to maintain IP66 rating use Atex rated glands and blanking plugs Taper glands and blanking plugs should use suitable thread seala...

Страница 4: ...cal applications would be boiler rooms school laboratories commercial kitchens etc Cabling should have a suitable level of protection for the area into which the detector is fitted and be of a screene...

Страница 5: ...is designed to take input from a standard pellistor and give either a linear 4 20mA current source output or digital RS485 addressable output Status LED s are provided to indicate mode of operation a...

Страница 6: ...rrent Note the meter will read half the head drive current Use the UP DOWN buttons to increase or decrease the set point Fault LED flashes on every button press For MK3 and MK5 IGD pellistors set to 1...

Страница 7: ...h the LED flashing connect a multimeter as indicated to read the CAL mA output Use the UP DOWN buttons to increase or decrease the set point Note that 12mA mid scale or 50 LEL is indicated on the mete...

Страница 8: ...ading to stabilise minimum of 60 seconds Press and hold either button until LED goes off then release LED s will then flash in turn for 5 seconds during zero The unit will then automatically return to...

Страница 9: ...possible to set other address combinations by connecting the unit to an IGD configuration terminal This should only be undertaken by trained technicians and is beyond the scope of this manual OLIVER I...