2.6.1 - Configuration of the electronics for low or high wall installation
The unit can be installed both in the lower part (adjacent to the floor) and in the upper
part (adjacent to the ceiling) of the wall.
To optimize air distribution and ambient comfort, the direction of the air flow can be
changed by changing the position of the air outlet flap.
Upper wall configuration determines an automatic correction of
the room temperature equal to 3°C in heating mode.
For correct functionality, each modification of the configuration of
the air outlet flap must correspond to the relative modification of
the electronic configuration.
In the configuration of high or low wall installation, the display shows 1
.
To set the desired configuration, carry out the previously described procedures and
choose between the parameter
(for roof installation) or
(for floor installation).
2.6.2 - Energy boost/System enable
configuration
The inlet located on the clamp
(Y2) of the main board (Y1) can
be used to activate the ENERGY
BOOST or SYSTEM ENABLE
functions of the air conditioner
(fig. 28).
In the configuration of the contact Energy boost or System enable, the display shows
.
The parameter can possess a value included between -5 and +5.
With value PI = 0, the inlet works from SYSTEM ENABLE.
When the contact opens, the air conditioner is forced in stand-by mode.
When the contact closes, the air conditioner restores the previous operating status.
With value
PI ≠ 0
, the inlet works from ENERGY BOOST.
Values <0 reduce the Tset in cooling, increasing machine power (for instance, if
Tset=24°C and Energy boost = -3°C, the machine works as if the Tset is 21°C)