24
These pages display the current errors and alarms active on the unit. After accessing the "Error" function,
you can browse any pages using the buttons on the left and right sides of the window.
NOTES:
1.
This function does not allow current errors to be reset; it only displays them.
2.
For more information about the error codes, refer to chapter 9.
3.
There may be several pages, depending on the number of errors (up to 5 errors per page).
6.4.
Viewing the active errors on the unit (Error)
These pages display the alarm log for the unit. After accessing the "Error" function, you can browse any
pages using the buttons on the left and right sides of the window.
NOTES:
1.
There may be several pages, depending on the number of errors; the log lists the last 20 errors.
2.
For more information about the error codes, refer to chapter 9.
6.5.
Viewing the error log (Error log)
These pages display the version of the software installed on the unit.
6.6.
Viewing software information (Version)
7.
COMMISSION
MENU
7.1.
Navigating the menu
WARNING: these functions and parameters must
only be set and/or modified by authorised person-
nel with the necessary technical skills to install and
maintain these units.
Incorrect settings may lead to malfunctioning or
damage to the unit and the system!
This menu is used to make the settings needed for
correct unit operation: the logics, the components in-
stalled on the system and the accessories envisaged
for each installation will be set using the functions in
this menu.
The information in the menu is sub-divided into two
large macro groups:
T
“Function“ (containing the settings and any
functions needed for unit operation)
T
“Parameter“ (containing the general operating
parameters)
Commission
Function
Param.
25
To navigate the “Function” or “Parameter“ sub-menu,
use the following keys:
T
(
1
) Move back to the previous page
T
(
2
) Move on to the next page
T
(
3
) Go back to the higher level menu
T
(
4
) Go back to the main page
T
To access a function, click on the text of that
function.
Function (1/4)
Ctrl. state: T water out
C l a valv : O
at a valv : Off
Solar setting: Without
Water tank: With
3
4
1
2
Parameter (1/1)
T HP max: 50°C
Cool run time: 5 min
Heat run time: 3 min
3
4
1
2
NB:
if the relative function is activated (paragraph 8.3), the value of these parameters will be stored in the
memory and automatically reset after any possible voltage failure.
After accessing the “Ctrl.state” function, you can
choose whether to base the unit control logic on the
processed water temperature or on the ambient air
temperature (if the air probe accessory is installed
and correctly set). Select the required logic, then press
“OK” to confirm.
Ctrl. state
T room
T water out
OK
Cancel
NOTES:
1.
If the ambient air probe accessory is not installed (and correctly set), you can only choose “T-water
out”.
2.
If the relative function is activated (paragraph 8.3), the value of these parameters will be stored in the
memory and automatically reset after any possible voltage failure.
7.2.
Setting the control logic (Ctrl.state)