Olimpia splendid INVERTER 12 HP Скачать руководство пользователя страница 9

 

 

8.1

 

External heat-exchanger temperature too high (HTE): 

 

The alarm occurs when the internal heat-exchanger temperature grows more than 70°C. The HTI alarm is cancelled 
when the internal heat-exchanger temperature reduces below than 60°C. Possible causes are: 
 
-  Presence of obstructions near the inlet and outlet pipes; 
-  Obstructions inside the machine; 
-  Excessive dirt accumulated on the outdoor heat-exchanger; 
-  Malfunction ODU fan  
-  High external air temperature   

  

8.2

 

Condensate max level alarm (OF): 

 
In case of condensate max level switch opens continuously for at least 1minute, the air-conditioner stops working 
(all  the  outputs  are  switched  off,  air-sweep  and  air-inlet  closes).  The  state  of  alarm  appears  on  the  display.  The 
alarm is disabled in fan mode or standby mode. The causes that may have caused the alarm activation are: 
 
- Lock or break the condensate pump;  
- Malfunction of the float activate pump; 
- Burning of the power transformer pump; 
 

8.3

 

Internal heat exchanger temperature too low (LT): 

 

The 

LT 

alarm occurs when the compressor is running, and the internal heat exchanger temperature is below -2°C 

for  more  than  5  minutes,  continuously.  The  alarm  is  cancelled  when  the  internal  heat-exchanger  temperature 
grows beyond 7°C. The causes that may have caused the alarm activation are: 
 
-  Presence of obstructions near the inlet and outlet pipes; 
-  Obstructions inside the machine; 
-  Excessive dirt accumulated on the indoor heat exchanger; 
-  Malfunction IDU fan  
-  Low external air temperature   
 

8.4

 

Internal heat exchanger temperature too high (HTI): 

 

The 

HTI 

alarm  occurs  when  the  internal  heat-exchanger  temperature  grows  more  than  65°C  and  it  is  cancelled 

when the internal heat-exchanger temperature reduces below than 42°C. The causes may be:  
 
- internal air filter clogged.  
- Internal heat-exchanger dirty  
- Indoor air fan blocked or slowed.  
- Suction screen clogged.  
- Outside air temperature is too high. The air conditioner can’t operate in heating with temperatures above 25°C. 
 - Indoor air temperature too high due to excessive layers in the room where the machine is installed. 
 

8.5

 

Discharge temperature too high 

 

The maximum threshold beyond which the alarm is activated is 110 ° C but there isn’t a lower limit temperature 
threshold for the automatic disabling of the alarm. 

 

9.

 

MANAGEMENT AND CONDENSATE DRAIN 

 
The  drain  pump  is  activated  only  when  the  compressor  is  ON  and  micro-switch  (pump  running)  closed.  A  second 
switch  operated  by  another  float  (high  water),  it  shall  stop  the  machine  if  it  remains  open  for  more  than  60 
seconds. If the contacts remain closed for more than a minute in fact, the shutter is powered (230 V) and discharge 
water to a maximum interval of 3 minutes or until the switches are not open.  
The  shutter  is  normally  scheduled  to  be  closed  in  the  state  of  standstill.  In  the  heating  mode  (pump  OFF)  card 
provides voltage electronic shutter to allow the discharge of water from the external heat-exchanger.  

 

 

Содержание INVERTER 12 HP

Страница 1: ...y Efficiency Class in cooling mode A A A A Energy Efficiency Class in heating mode _ A _ A Fan speed indoor outdoor 3 4 3 4 3 4 3 4 Room air volume in cooling mode max med min m h 490 430 360 490 430...

Страница 2: ...ilters the machine doesn t stop it is reset by pressing the micro button for a few seconds 3 REMOTE CONTROL T1 ON OFF standby T2 Economy key T3 Night key T4 Operating mode selector T5 Fan speed select...

Страница 3: ...minute When time ends the compressor continues to work in according to procedure described below frequency is recalculated every 3 minutes T room T set 3 C MAXIMUM frequency T set 3 C T room T set 1 C...

Страница 4: ...Hz and then work at least for 28 sec after which the outdoor fan is turned off After another 2 sec also 4 ways valve is disabled so the compressor increases the frequency to the limit of 60 Hz The def...

Страница 5: ...um speed and the T set is automatically increased by 1 C after 1 hour and by a further 1 C after 2 hours In heating mode when the night mode is enabled the internal fan is forced to minimum speed exte...

Страница 6: ...2 minutes after that the limit was overtaken In case of air conditioner is turned on with T discharge on the limit compressor starts to work The frequency is limited to the first compressor frequency...

Страница 7: ...n T camb amounted to 3 C it is not possible to separate two operations Figure 1 refers to a machine configured for installation near the floor in which air flows upwards The same configuration may als...

Страница 8: ...in real time DIAGNOSTIC ALARMS CONTROL MODULE blinking on display Tripping threshold LED D green LED C yellow LED B green LED A red T room sensor fault open short circuit 0 1 T int heat exchanger sen...

Страница 9: ...side the machine Excessive dirt accumulated on the indoor heat exchanger Malfunction IDU fan Low external air temperature 8 4 Internal heat exchanger temperature too high HTI The HTI alarm occurs when...

Страница 10: ...10 SCHEMATIC...

Страница 11: ...9 1 Control board side...

Страница 12: ...9 2 IPM board side...

Страница 13: ...11 OHMICH VALUES COMPRESSOR DISCHARGE SENSOR...

Страница 14: ...12 OHMICH LVALUES HEAT EXCHANGER AND AIR SENSOR...

Страница 15: ...13 ACCESSORIES Currently there aren t accessories except those supplied with the machine...

Отзывы: