4.

 

MODE AND LOGIC OPERATION 

 

4.1

 

Automatic mode: 

 

These  mode  can  be  selected  from  the  Remote  Control  by  acting  on  the  relative  key  as  well  as  by  pressing  the 
switch on the display card (in the latter case, only if the appliance was formerly in standby mode). In this program 
the appliance working mode is selected automatically depending on the room temperature value monitored: 
 

 

T°room < 17°C   

 

(heating) 

 

IDU maximum speed enabled; 

 

 

17°C ≤ T°room < 19°C   

(heating) 

 

IDU medium speed enabled;; 

 

 

19°C ≤ T°room < 21°C   

(heating) 

 

IDU minimum speed enabled; 

 

 

21°C ≤ T°room ≤ 23°C   

(ventilation only) 

IDU minimum speed enabled; 

 

 

23°C < T°room ≤ 25°C   

(cooling) 

 

IDU minimum speed enabled; 

 

 

25°C < T°room ≤ 27°C   

(cooling) 

 

IDU medium speed enabled; 

 

 

T°room > 27°C   

 

(cooling) 

 

IDU maximum speed enabled; 

 

4.2

 

Cooling mode: 

 

In  this  mode,  the  air  conditioner  dehumidifies  and  cools  the  room.

 

Before  carrying  out  the  operation,  set  the 

required temperature and  choose the fan speed (refer to the related  paragraphs). After having activated this run 
mode, the compressor will start running after 3 minutes at the most and the unit will begin to emit cold air; 

if the 

temperature  is  below  the  set  temperature  the  compressor  doesn’t  start.  Only  at  first  start-up  from  power  off,  if 
T°room  is  higher  than  T°set,  T°room  is  forced  by  IDU  board  to  45°C  in  order  to  force  the  compressor  to  the 
maximum  frequency  for  1  minute.  When  time  ends,  the  compressor  continues  to  work  in  according  to  procedure 
described 

below

 (frequency is recalculated every 3 minutes):

 

 

  

 

T°room ≥ T°set +3°C    

 

 

MAXIMUM frequency; 

 

 

T°set +3°C > T°room. ≥ T°set +1°C  

 

MODULATED frequency; 

 

 

T°set -1°C ≤ T°room. ≤ T°set +1°C  

 

MINIMUM frequency; 

 

 

T°room ≤ T°set-1°C  

 

 

 

compressor OFF; 

 
The  IDU  FAN

 

motor  works  at  selected  speed  (MIN,  MED  or  MAX  depending  on  Remote  Control  setting).  In  case 

automatic speed mode is enabled, IDU FAN speed works in this way (in case T°room changes instead, the automatic 
speed waits at least 3 min. working at the same speed before changing): 
 

 

T°room. ≤ T°set+1°C    

 

MINIMUM speed; 

 

 

T°set +1°C < T°room. ≤ T°set +3°C 

MEDIUM speed; 

 

 

T°room. > T°set+3°C    

 

MAXIMUM speed; 

 

4.3

 

Heating mode (heating pump only): 

 

First  set  the  desired  temperature  and  fan  speed.  After  three  minutes  the  compressor  should  start  and  the  air 
conditioner starts heating the room. The start of the compressor can be checked through the lighting of the green 
LED located on the console. 

It’s only available for models with heat pump (HP). This operation must be preceded by 

the setting of desired temperature and fan speed selection. Only at first start-up from power off, if T°set deviates 
± 1°C from the value measured in,  the temperature of the room is forced to 5°C in order to force the compressor 
frequency for a maximum interval of 1 minute.

 

When time ends, the compressor continues to work in according to 

procedure described below where T°camb. corresponds to environment temperature correction on the location of 
the high/low unit (see cap.6):  

Содержание INVERTER 12 HP

Страница 1: ...y Efficiency Class in cooling mode A A A A Energy Efficiency Class in heating mode _ A _ A Fan speed indoor outdoor 3 4 3 4 3 4 3 4 Room air volume in cooling mode max med min m h 490 430 360 490 430...

Страница 2: ...ilters the machine doesn t stop it is reset by pressing the micro button for a few seconds 3 REMOTE CONTROL T1 ON OFF standby T2 Economy key T3 Night key T4 Operating mode selector T5 Fan speed select...

Страница 3: ...minute When time ends the compressor continues to work in according to procedure described below frequency is recalculated every 3 minutes T room T set 3 C MAXIMUM frequency T set 3 C T room T set 1 C...

Страница 4: ...Hz and then work at least for 28 sec after which the outdoor fan is turned off After another 2 sec also 4 ways valve is disabled so the compressor increases the frequency to the limit of 60 Hz The def...

Страница 5: ...um speed and the T set is automatically increased by 1 C after 1 hour and by a further 1 C after 2 hours In heating mode when the night mode is enabled the internal fan is forced to minimum speed exte...

Страница 6: ...2 minutes after that the limit was overtaken In case of air conditioner is turned on with T discharge on the limit compressor starts to work The frequency is limited to the first compressor frequency...

Страница 7: ...n T camb amounted to 3 C it is not possible to separate two operations Figure 1 refers to a machine configured for installation near the floor in which air flows upwards The same configuration may als...

Страница 8: ...in real time DIAGNOSTIC ALARMS CONTROL MODULE blinking on display Tripping threshold LED D green LED C yellow LED B green LED A red T room sensor fault open short circuit 0 1 T int heat exchanger sen...

Страница 9: ...side the machine Excessive dirt accumulated on the indoor heat exchanger Malfunction IDU fan Low external air temperature 8 4 Internal heat exchanger temperature too high HTI The HTI alarm occurs when...

Страница 10: ...10 SCHEMATIC...

Страница 11: ...9 1 Control board side...

Страница 12: ...9 2 IPM board side...

Страница 13: ...11 OHMICH VALUES COMPRESSOR DISCHARGE SENSOR...

Страница 14: ...12 OHMICH LVALUES HEAT EXCHANGER AND AIR SENSOR...

Страница 15: ...13 ACCESSORIES Currently there aren t accessories except those supplied with the machine...

Отзывы: