error is automatically restored and the indicator
is turned OFF.
TESTS
Normally the illumination source and the
autonomy tests are programmed by the
control panel and the test results are sent to
the control panel.
If the luminaire is not connected to GR-
6500 panel, the following automatic tests
executed:
AUTOMATIC EMERGENCY CIRCUIT TEST
The unit automatically tests the emergency
circuit every 15 days (if the battery and mains
power are connected). During this test the
lamps are turned ON for 3 seconds using the
batteries. In some cases this function might not
be acceptable (i.e in cinema theaters) so the
installer must take this into account during the
installation.
AUTOMATIC DURATION TEST
This test is conducted every 6 months by
simulating a power failure, if the battery and
mains power supply are connected. The unit
lights the lamps using the charged battery and
counts the time until the stated duration. If the
lamps are ON during the end of the test then the
unit is restored to its normal operation (lamps
OFF and battery charging). If the lamps go OFF
before the end of the test then the unit is
restored to its normal operation but the LAMP
FAULT / BATT. FAULT indicator is lit to show that
there is a problem with the battery and that the
battery must be replaced. Let it be noted that
this duration test is also done during every long
power failure. If the power failure lasts for a long
time and the luminaire has entered the
BATTERY CUTOFF mode and the duration
measured is not correct then the fault indicator
will light when the power is restored.
ERASING ERRORS
Erasing errors is accomplished with a prolonged
pressing of the TEST button (>5 sec) when the
unit is connected to the mains power supply.
The fault indicated with the indicator LAMP
FAULT / BATT. FAULT will be erased. If the
cause of the fault has not been restored (i.e
burned lamp) then the indicator will light again. If
the fault was caused by a low emergency
duration and you erase the error then this will be
indicated again during the next duration test
after 6 months. In this case (for duration errors)
it is vital to replace the battery before erasing the
error (the error is automatically erased if the
mains power and the battery are disconnected).
WARNING !!!
1. Every test, installation or maintenance
procedure must be done only by qualified
personnel.
2.
The unit must be connected to the mains
p o w e r s u p p l y u s i n g a l i n e f u s e r a t e d
accordingly.
3.
The replacement of the battery and the light
source must be done using parts of the same
type, by the manufacturer or by a competent
person.
4.
If the luminaire must be isolated from the
mains power supply for more than 2 months
then the batteries must be disconnected by
removing the battery connectors.
5.
I s not allowed to discard batteries in to
t i
common trash bins, they must be
discarded only
in battery recycling
points. Do not incinerate.
INSTALLATION
To install the luminaire follow the installation
procedure as described on page 3
.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
0:
Non Maintained (*)
A:
Including test device
B:
Including remote rest mode
C:
Including inhibiting mode
*90:
1.5 hour duration
180:
3 hour duration
(*)
Non Maintained operation: The luminaire
lights its illumination source,
only in power
supply’s failure.
Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not
.
Battery replacement
.
It can be done only by a competent person
and after the mains interruption
.
1.
Follow the step 2
o
f the installation
procedure.
2.
Disconnect the
cables
and remove the old
battery.
3.
Connect the new battery with the same type
(step
3
of the installation procedure) and place
it in the
position
of the old one.
4.
Follow the step
6
of the installation
procedure and
power the device.
The light source contained in this
luminaire shall only be replaced by the
manufacturer, or his agent, or a similar
qualified person.
NOTE! The light source is non-user
replaceable.
923039006_09_001