background image

Page

 

2

 

from

 

6

error is automatically restored and the indicator 
is turned OFF.

TESTS

Normally  the  illumination  source  and  the 
autonomy  tests  are  programmed  by  the 
control  panel  and  the  test  results  are  sent  to 
the control panel.

If  the  luminaire  is  not  connected  to  GR-
6500  panel,  the  following  automatic  tests 
executed: 

AUTOMATIC EMERGENCY CIRCUIT TEST

The  unit  automatically  tests  the  emergency 
circuit every 15 days (if the battery and mains 
power  are  connected).  During  this  test  the 
lamps  are  turned  ON  for  3  seconds  using  the 
batteries. In some cases this function might not 
be  acceptable  (i.e  in  cinema  theaters)  so  the 
installer must take this into account during the 
installation.

AUTOMATIC DURATION TEST

This  test  is  conducted  every  6  months  by 
simulating  a  power  failure,  if  the  battery  and 
mains  power  supply  are  connected.  The  unit 
lights the lamps using the charged battery and 
counts the time until the stated duration. If the 
lamps are ON during the end of the test then the 
unit is restored to its normal operation (lamps 
OFF and battery charging). If the lamps go OFF 
before  the  end  of  the  test  then  the  unit  is 
restored to its normal operation but the LAMP 
FAULT / BATT. FAULT indicator is lit to show that 
there is a problem with the battery and that the 
battery  must  be  replaced.  Let  it  be  noted  that 
this duration test is also done during every long 
power failure. If the power failure lasts for a long 
time  and  the  luminaire  has  entered  the 
BATTERY  CUTOFF  mode  and  the  duration 
measured is not correct then the fault indicator 
will light when the power is restored.

ERASING ERRORS

Erasing errors is accomplished with a prolonged 
pressing of the TEST button (>5 sec) when the 
unit  is  connected  to  the  mains  power  supply. 
The  fault  indicated  with  the  indicator    LAMP 
FAULT  /  BATT.  FAULT  will  be  erased.  If  the 
cause  of  the  fault  has  not  been  restored  (i.e 
burned lamp) then the indicator will light again. If 
the  fault  was  caused  by  a  low  emergency 
duration and you erase the error then this will be 
indicated  again  during  the  next  duration  test 
after 6 months. In this case (for duration errors) 
it is vital to replace the battery before erasing the 
error  (the  error  is  automatically  erased  if  the 
mains power and the battery are disconnected).

WARNING !!!

1. Every test, installation or maintenance

procedure must be done only by qualified
personnel.

2.

  The  unit  must  be  connected  to  the  mains 

p o w e r   s u p p l y   u s i n g   a   l i n e   f u s e   r a t e d  
accordingly.

3.

 The replacement of the battery and the light 

source must be done using parts of the same 
type,  by  the  manufacturer  or  by  a  competent 
person.

4. 

If  the  luminaire  must  be  isolated  from  the 

mains  power  supply  for  more  than  2  months 
then  the  batteries  must  be  disconnected  by 
removing the battery connectors.

5. 

I s not allowed to discard batteries in to 

t i

common  trash  bins,  they  must  be 
discarded  only 

 

in  battery  recycling 

points. Do not incinerate.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
procedure as described on page 3

.

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained 

  

0: 

Non Maintained (*)

A: 

Including test device 

 

B: 

Including remote rest mode

C: 

Including inhibiting mode

*90: 

1.5 hour duration 

180: 

3 hour duration

(*)

Non  Maintained  operation:  The  luminaire 

lights  its  illumination  source,

 

only  in    power 

supply’s failure. 

 

Maintained  operation:  The  luminaire  lights  its 
illumination source, when it is powered by the 
mains power supply or not

 

Battery replacement

It can be done only by a competent person 
and after the mains interruption

.

1.

  Follow  the  step  2 

o

f  the  installation 

procedure.

2.

  Disconnect  the 

cables

  and  remove  the  old 

battery.

3.

 Connect the new battery with the same type 

(step

 3

 of the installation procedure) and place 

it in the

 

position

  

of the old one.

4.

  Follow  the  step 

6

  of  the  installation 

procedure and

 

power the device.

The light source contained in this 

luminaire shall only be replaced by the 
manufacturer, or his agent, or a similar 

qualified person.

NOTE! The light source is non-user 
replaceable.

923039006_09_001

Содержание POWER LIGHT Series

Страница 1: ...not been connected If the batteries are connected and the indicator does not light then contact a qualified service technician for assistance The charging procedure is monitored by a microprocessor and is based on a 3 stage cycle thus ensuring a fast and full charge of the battery The charge current is supplied by a high efficiency switch mode power supply which ensures perfect charging even durin...

Страница 2: ...t again If the fault was caused by a low emergency duration and you erase the error then this will be indicated again during the next duration test after 6 months In this case for duration errors it is vital to replace the battery before erasing the error the error is automatically erased if the mains power and the battery are disconnected WARNING 1 Every test installation or maintenance procedure...

Страница 3: ...retaining screws 1 Use the supplied mounting accessories to mount the device fig1 2 Remove the four cover retaining screws fig 1 3 Instal the battery cable connectors to the batteries taking care of the polarity black cable and red cable 4 Always use in any case round mains cable with external diameter of 6 9mm H05RN F type 2x1mm or any other type at least equal to it s mechanical and electrical p...

Страница 4: ...5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2...

Страница 5: ...8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 ...

Страница 6: ... technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or replacement as long as the warranty period is valid Olympia E...

Отзывы: